Appendix 4 List of Special Register (SD) Areas
Description
Details
Details of the invalid
• When an invalid power supply module exists, the status is stored using
power supply
the following bit pattern.
module
• Bits corresponding to power-off or empty slots for the power supply
0: Valid/power-off/
module turn off.
no power supply
• When the main base unit is not the redundant power supply main base
module
unit, 0 is stored.
■Details of the invalid power supply module (power supply module 1)
1: Invalid
b0: Main base unit
b1: 1st extension base unit
b2: 2nd extension base unit
b7: 7th extension base unit
■Details of the invalid power supply module (power supply module 2)
b8: Main base unit
b9: 1st extension base unit
b10: 2nd extension base unit
b15: 7th extension base unit
Set by (setting
timing)
S (Status change)