Error
Error name
Error details and cause
code
2044H
Remote head
The own remote head No. set in the
module
system parameters ("I/O Assignment
configuration
Setting" in the [I/O Assignment] tab of
error
the "System Parameter" window) differs
from the one determined by the
mounting position of the remote head
module.
2050H
Remote head
An unsupported CPU module or remote
module
head module is mounted.
configuration
error
2060H
Base unit
Eight or more extension base units are
configuration
connected.
error
2061H
Base unit
Any of the following base units is
configuration
connected: QA1S3B, QA1S5B/
error
QA1S6B, QA6B, QA6ADP+A5B/
A6B, or QA1S6ADP+A1S5B/
A1S6B.
2063H
Base unit
Extension base unit levels are
configuration
overlapping.
error
2070H
Base unit
• An unsupported base unit is
configuration
connected.
error
• A GOT is bus-connected to the Q
series extension base unit.
2080H
Inter-module
An inter-module synchronization signal
synchronization
error has been detected.
configuration
error
20E0H
Invalid module
A module that the remote head module
cannot recognize is mounted.
2180H
Invalid file
An invalid file has been detected.
21A2H
File
A file other than the remote head
specification
module project file has been written.
error
2220H
Parameter
The parameter setting is corrupted.
error
Action
Re-set the own remote head No. in the system
parameters in accordance with the mounting
position of the remote head module.
Remove the unsupported CPU module or remote
head module.
If all the remote head modules are supported, the
possible cause is a hardware failure of the remote
head module or base unit. Please consult your
local Mitsubishi representative.
Reduce the number of extension base units to
seven or less.
Remove the inapplicable base unit: QA1S3B,
QA1S5B/QA1S6B, QA6B, QA6ADP+A5B/
A6BB, and QA1S6ADP+A1S5B/A1S6B.
Check and correct the level setting of the
extension base units.
• Disconnect the unsupported base unit. If all the
base units are supported, the possible cause is
a hardware failure of the remote head module or
base unit. Please consult your local Mitsubishi
representative.
• Disconnect the GOT bus-connected to the Q
series extension base unit.
The possible cause is a hardware failure of the
remote head module, base unit, or module (I/O
module or intelligent function module) connected.
Please consult your local Mitsubishi
representative.
• Mount only applicable modules.
• The possible cause is a hardware failure of the I/
O module or intelligent function module
accessed. Please consult your local Mitsubishi
representative.
Check the detailed information (drive/file
information) of the error by executing module
diagnostics using the engineering tool, select the
correct file name, and write the specified file to the
remote head module. If the same error code is
displayed again, the possible cause is a hardware
failure of the remote head module. Please consult
your local Mitsubishi representative.
Check the detailed information (parameter
information) of the error by executing module
diagnostics using the engineering tool, and
overwrite the file corresponding to the displayed
number (file name.extension) with the one created
in the project of the remote head module.
Check the detailed information (parameter
information) of the error by executing module
diagnostics using the engineering tool, and write
the displayed parameter setting to the remote
head module. If the same error code is displayed
again, the possible cause is a hardware failure of
the data memory in the remote head module or the
module (I/O module or intelligent function module)
connected. Please consult your local Mitsubishi
representative.
Detailed
Diagnostic
information
timing
System
System
configuration
configuration
information
information
System
System
configuration
configuration
information
information
System
At power-on,
configuration
at RESET
information
System
At power-on,
configuration
at RESET
information
System
At power-on,
configuration
at RESET
information
System
At power-on,
configuration
at RESET
information
System
At power-on,
configuration
at RESET
information
System
Always
configuration
information
Drive/file
Always
information
Drive/file
At write, at
information
power-on, at
RESET, at
STOP  RUN
state
Parameter
At power-on,
information
at RESET, at
STOP  RUN
state
4 TROUBLESHOOTING
109
4.7 Error Codes
4

Advertisement

Table of Contents
loading

Table of Contents