1.3

Remote Operation

The operating status of the remote head module can be changed using an engineering tool or dedicated instructions from the
module. The following types of remote operation are available:
• Remote RUN/STOP
• Remote RESET
Remote RUN/STOP
This function remotely changes the operating status of the remote head module to RUN or to STOP, keeping the switch of the
remote head module at the RUN position. This function is useful to run or stop a remote head module located in an
inaccessible place or in the control panel by using external signals.
When the switch of the remote head module is at the STOP position, or when the CPU module on the master
station is in the STOP state (including disconnection), even if remote RUN is performed, the remote head
module will not enter the RUN state.
Executing method
The following methods are available,
■Using an engineering tool
• From the menu, open the "Remote Operation" window to execute the function. ( GX Works3 Operating Manual)
[Online]  [Remote Operation]
• Execute the function using the CC-Link IE Field Network diagnostics. ( Page 96 Remote operation)
■By an external device using SLMP
Execute the function with the SLMP command. ( SLMP Reference Manual)
■Using the module dedicated instructions
Execute the function with the dedicated instructions of a network module. ( MELSEC iQ-R Programming Manual
(Instructions, Standard Functions/Function Blocks))