Mitsubishi Electric MELSEC iQ-R Series User Manual page 117

Cc-link ie field network remote head module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Error
Error name
Error details and cause
code
3006H
Pairing setting
Pairing is not set to the stations in a
error
redundant system.
3007H
Pairing setting
Pairing is set to the stations not included
error
in a redundant system.
3040H
Response data
Response data of the dedicated
creation failure
instruction cannot be created.
3200H
Label
Memory/Device Setting set in the CPU
information
parameters differ from those assigned to
mismatch
the global label setting file.
3205H
Label
• After the global label setting file was
information
modified, only the modified file was
mismatch
written to the remote head module. Or,
after the global label setting file was
modified, only the CPU parameters
were written to the remote head
module. (The global label setting file
was not written to the remote head
module.)
• After the CPU parameters were
modified, only the CPU parameters
were written to the remote head
module.
• After the external device access
setting of the global label setting was
modified, only the global label
assignment information was written to
the remote head module. Or, after the
external device access setting of the
global label setting was modified, only
the CPU parameters were written to
the remote head module. (The
external device access setting of the
global label setting file was not written
to the remote head module.)
3206H
Label
After the global label setting file was
information
modified, only the modified file was
mismatch
written to the remote head module. Or,
without writing the modified global label
setting file, only the initial global label
value file was written to the remote head
module.
3600H
Inter-module
The value of the inter-module
synchronization
synchronization cycle setting differs from
cycle mismatch
the one set in the master station.
3601H
Inter-module
In the network synchronous
synchronization
communication setting of the network
cycle mismatch
configuration setting of the master
station, the own station is not set as a
target of inter-module synchronization.
3602H
Inter-module
Inter-module synchronization cycle
synchronization
failure occurred between networks.
signal failure
via network
Action
Check the pairing setting in the network
configuration setting of the master station.
Check the pairing setting in the network
configuration setting of the master station.
• Increase the request interval.
• Decrease the number of request nodes.
• Wait for a response to the previous request
before sending the next request.
• Correct the timeout value.
• Write the global label setting file together with
the CPU parameter file to the remote head
module.
• If no global label is used, delete the global label
setting file.
• Write CPU parameters, global label setting, and
global label assignment information files to the
remote head module.
• If no global label is used, delete the global label
setting file.
• If the external device access setting is not used,
initialize the memory where the global label
assignment information file is stored, and write
the CPU parameters and global label setting file
to the remote head module.
• Write both the global label setting file and initial
global label value file to the remote head
module.
• If no initial global label value is used, delete the
initial global label value file.
Correct the parameter so that all modules
performing inter-module synchronization have the
same frequency setting.
Check the network configuration setting of the
master module and check if inter-module
synchronization is set.
• Check the network status and take corrective
action using the CC-Link IE Field Network
diagnostics.
• Check if the switching hub and the cables are
connected properly.
• If the error occurs again even after taking the
above, please consult your local Mitsubishi
representative.
Detailed
Diagnostic
information
timing
Parameter
At power-on,
information
at RESET
Parameter
At power-on,
information
at RESET
Always
Drive/file
At power-on,
information
at RESET, at
STOP  RUN
state
Drive/file
At power-on,
information
at RESET, at
STOP  RUN
state
Drive/file
At power-on,
information
at RESET, at
STOP  RUN
state
Parameter
Always
information
Parameter
Always
information
Always
4 TROUBLESHOOTING
115
4.7 Error Codes
4

Advertisement

Table of Contents
loading