Par. No.
Name
p0977
Save all parameters
Description: Saves all parameters of the drive system to the non-volatile memory.
When saving, only the adjustable parameters intended to be saved are taken into account.
Value = 0: Inactive
Value = 1: Save in non-volatile memory - downloaded at POWER ON
Notice: The Control Unit power supply may only be powered down after data has been saved (i.e. after data
save has been started, wait until the parameter again has the value 0).
Writing to parameters is inhibited while saving.
p1058
JOG 1 speed setpoint
Description: Sets the speed/velocity for JOG 1. Jogging is level-triggered and allows the motor to be incre-
mentally moved.
Note: The parameter values displayed on the BOP are integers.
p1082 *
Maximum speed
Description: Sets the highest possible speed.
Notice: After the value has been modified, no further parameter modifications can be made.
Note: The parameter values displayed on the BOP are integers.
The parameter applies for both motor directions.
The parameter has a limiting effect and is the reference quantity for all ramp-up and ramp-down times (e.g.
down ramps, ramp-function generator and motor potentiometer).
The range of the parameter is different when connect with different motors.
p1083 *
Speed limit in positive
direction of rotation
Description: Sets the maximum speed for the positive direction.
Note: The parameter values displayed on the BOP are integers.
p1086 *
Speed limit in negative
direction of rotation
Description: Sets the speed limit for the negative direction.
Note: The parameter values displayed on the BOP are integers.
p1115
Ramp-function generator
selection
Description: Sets the ramp-function generator type.
Note: Another ramp-function generator type can only be selected when the motor is at a standstill.
p1120
Ramp-function generator
ramp-up time
Description: The ramp-function generator ramps-up the speed setpoint from standstill (setpoint = 0) up to the
maximum speed (p1082) in this time.
Dependency: Refer to p1082
p1121
Ramp-function generator
ramp-down time
Description: Sets the ramp-down time for the ramp-function generator.
The ramp-function generator ramps-down the speed setpoint from the maximum speed (p1082) down to
standstill (setpoint = 0) in this time.
Further, the ramp-down time is always effective for OFF1.
Dependency: Refer to p1082
Getting Started
A5E37208904-003, 04/2017
Min
Max
0
1
0.00
210000.000 100.00
0.000
210000.000 1500.00
0.000
210000.000 210000.
-210000.000
0.000
0
1
0.000
999999.000 1
0.000
999999.000 1
Factory
Unit
Data
Setting
type
0
-
U16
rpm
Float
rpm
Float
0
rpm
Float
000
-
rpm
Float
210000.
000
0
-
I16
s
Float
s
Float
Effective
Can be
changed
IM
T, U
IM
T
IM
T
IM
T, U
IM
T, U
IM
T
IM
T, U
IM
T, U