Connecting the cable shields with the shielding plate
To achieve EMC-compliant installation of the drive, use the shielding plate that is shipped with the drive to connect the cable
shields. See the following example for steps of connecting cable shields with the shielding plate:
DANGER
Death or severe personal injury from electrical shock
The earth leakage current for the drive can be greater than AC 3.5 mA, which may cause death or severe
personal injury due to electrical shock.
A fixed earth connection is required to eliminate the dangerous leakage current. In addition, the minimum size
of the protective earth conductor shall comply with the local safety regulations for high leakage current
equipment.
Getting Started
A5E37208904-003, 04/2017
43