GE Multilin 469 Instruction Manual page 300

Motor management relay
Table of Contents

Advertisement

7.2.7
Analog Inputs and Outputs
7–8
INPUT
ACCESS
TEST
STARTER STATUS
EMERGENCY RESTART
REMOTE RESET
ASSIGNABLE INPUT 1
ASSIGNABLE INPUT 2
ASSIGNABLE INPUT 3
ASSIGNABLE INPUT 4
TRIP COIL SUPERVISION
The 469 specification for analog input and analog output accuracy is ±1% of full scale.
Perform the steps below to verify accuracy. Verify the Analog Input +24 V DC with a
voltmeter.
4 to 20 mA Analog Input
Alter the following settings:
S12 ANALOG I/O
S12 ANALOG I/O
S12 ANALOG I/O
value for Analog Inputs 2 to 4)
Analog output values should be ±0.2 mA on the ammeter. Measured analog input
values should be ±10 units.
Force the analog outputs using the following settings:
S13 TESTING
TEST ANALOG OUTPUT
"Enabled"
S13 TESTING
TEST ANALOG OUTPUT
(enter desired value in percent; repeat for Analog Outputs 2 through 4)
Verify the ammeter readings as well as the measured analog input
readings.
For the purposes of testing, the analog input is fed in from the analog
output (see FIGURE 7–1: Secondary Injection Test Setup on page 7–2).
View the measured values in:
A1 STATUS
DIGITAL INPUTS
EXPECTED
PASS /
STATUS (SWITCH
FAIL
OPEN)
Open
Open
Open
Open
Open
Open
Open
Open
Open
No Coil
ANALOG INPUT1
ANALOG INPUT1:
ANALOG INPUT1
ANALOG INPUT1 MINIMUM:
ANALOG INPUT1
ANALOG INPUT1 MAXIMUM:
FORCE ANALOG OUTPUTS FUNCTION:
ANALOG OUTPUT 1 FORCED VALUE:
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 7: TESTING
EXPECTED
PASS /
STATUS (SWITCH
FAIL
CLOSED)
Shorted
Shorted
Shorted
Shorted
Shorted
Shorted
Shorted
Shorted
Shorted
Coil
"4-20 mA"
"0"
"1000" (repeat this
"0%"