CHAPTER 5: SETTINGS
OVERLOAD
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
Custom Overload Curve
If the
SELECT CURVE STYLE
will appear:
PATH: SETTINGS
S5 THERMAL MODEL
[
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
is set to "Custom" in the Thermal Model, the following settings
OVERLOAD CURVE SETUP
TIME TO TRIP AT
1.01 x FLA:
TIME TO TRIP AT
1.05 x FLA:
TIME TO TRIP AT
1.10 x FLA:
TIME TO TRIP AT
1.20 x FLA: 795.4
TIME TO TRIP AT
1.30 x FLA: 507.2
TIME TO TRIP AT
1.40 x FLA: 364.6
TIME TO TRIP AT
1.50 x FLA: 280.0
TIME TO TRIP AT
1.75 x FLA: 169.7
TIME TO TRIP AT
2.00 x FLA: 116.6
TIME TO TRIP AT
2.25 x FLA: 86.1
TIME TO TRIP AT
2.50 x FLA: 66.6
TIME TO TRIP AT
2.75 x FLA: 53.3
TIME TO TRIP AT
3.00 x FLA: 43.7
TIME TO TRIP AT
3.25 x FLA: 36.6
TIME TO TRIP AT
3.50 x FLA: 31.1
TIME TO TRIP AT
3.75 x FLA: 26.8
TIME TO TRIP AT
4.00 x FLA: 23.3
TIME TO TRIP AT
4.25 x FLA: 20.5
TIME TO TRIP AT
4.50 x FLA: 18.2
Range: 0.5 to 99999.9 s in steps of 0.1
Range: 0.5 to 99999.9 s in steps of 0.1
Range: 0.5 to 99999.9 s in steps of 0.1
Range: 0.5 to 99999.9 s in steps of 0.1
Range: 0.5 to 99999.9 s in steps of 0.1
Range: 0.5 to 99999.9 s in steps of 0.1
Range: 0.5 to 99999.9 s in steps of 0.1
Range: 0.5 to 99999.9 s in steps of 0.1
Range: 0.5 to 99999.9 s in steps of 0.1
Range: 0.5 to 99999.9 s in steps of 0.1
Range: 0.5 to 99999.9 s in steps of 0.1
Range: 0.5 to 99999.9 s in steps of 0.1
Range: 0.5 to 99999.9 s in steps of 0.1
Range: 0.5 to 99999.9 s in steps of 0.1
Range: 0.5 to 99999.9 s in steps of 0.1
Range: 0.5 to 99999.9 s in steps of 0.1
Range: 0.5 to 99999.9 s in steps of 0.1
Range: 0.5 to 99999.9 s in steps of 0.1
Range: 0.5 to 99999.9 s in steps of 0.1
5–43