GE Multilin 469 Instruction Manual page 213

Motor management relay
Table of Contents

Advertisement

CHAPTER 5: SETTINGS
5.9.2
RTDs 1 to 6
#1
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
Temperature
° C
° F
170
338
180
356
190
374
200
392
210
410
220
428
230
446
240
464
250
482
PATH: SETTINGS
S8 RTD TEMPERATURE
RTD
[ ]
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
Table 5–2: RTD Temperature vs. Resistance
100 Ω Pt
120 Ω Ni
(DIN 43760)
164.76
269.91
168.47
280.77
172.46
291.96
175.84
303.46
179.51
315.31
183.17
327.54
186.82
340.14
190.45
353.14
194.08
366.53
RTD #1(6)
RTD #1 APPLICA-
TION:
RTD #1 NAME:
RTD #1 ALARM:
Off
ASSIGN ALARM
RELAYS:
RTD #1 ALARM
TEMPERATURE:
RTD #1 HIGH
ALARM:
HIGH ALARM
RELAYS:
RTD #1 HIGH ALARM
TEMPERATURE:
RTD #1 ALARM
EVENTS: Off
RTD #1 TRIP:
Off
RTD #1 TRIP VOT-
ING:
ASSIGN TRIP
RELAYS:
100 Ω Ni
10 Ω Cu
224.92
15.61
233.97
16.00
243.30
16.39
252.88
16.78
262.76
17.17
272.94
17.56
283.45
17.95
294.28
18.34
305.44
18.73
Range: Stator, Bearing, Ambient, Other,
None
Range: 8 alphanumeric characters
Range: Off, Latched, Unlatched
Range: Alarm, Alarm & Auxiliary2,
Alarm & Aux2 & Aux3, Alarm &
Auxiliary3, Auxiliary2, Aux2 &
Aux3, Auxiliary3
Range: 1 to 250°C in steps of 1
Range: Off, Latched, Unlatched
Range: Alarm, Alarm & Auxiliary2,
Alarm & Aux2 & Aux3, Alarm &
Auxiliary3, Auxiliary2, Aux2 &
Aux3, Auxiliary3
Range: 1 to 250 in steps of 1
Range: On, Off
Range: Off, Latched, Unlatched
Range: RTD #1 to RTD #12
Range: Trip, Trip & Auxiliary2, Trip &
Aux2 & Aux3, Trip & Auxiliary3
5–71

Advertisement

Table of Contents
loading

Table of Contents