CHAPTER 5: SETTINGS
5.2.2
Preferences
PREFERENCES
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
PATH: SETTINGS
S1 469 SETUP
[
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
Some characteristics can be modified for different situations. Normally this subgroup will
not require changes.
DEFAULT MESSAGE CYCLE TIME: If multiple default messages are chosen, the display
automatically cycles through those messages. The display time can be changed to
accommodate different user preferences.
DEFAULT MESSAGE TIMEOUT: If no keys are pressed for a period of time, the relay
automatically scans a programmed set of default messages. This time can be user-
defined to ensure messages remain on the screen for a suitable time while entering
settings or actual values. Once default scanning starts, pressing any key returns the
last message viewed.
AVERAGE MOTOR LOAD CALCULATION PERIOD: This settings adjusts the period of
time over which the average motor load is calculated. The calculation is a sliding
window and is ignored during motor starting.
TEMPERATURE DISPLAY: Temperature measurements may be displayed in either
Celsius or Fahrenheit. Each temperature value is displayed as °C or °F. RTD settings are
always displayed in degrees Celsius.
TRACE MEMORY TRIGGER POSITION: Sets the trigger position for waveform capture.
This value represents the percentage of cycles captured and recorded in the trace
memory buffer prior to the trigger (trip).
TRACE MEMORY BUFFERS: Sets the number of traces to capture and the number of
cycles for each of the 10 waveforms captured. Note: 10 waveforms are captured for
each trace, showing all currents and voltages.
DISPLAY UPDATE INTERVAL: Sets the duration for which the metered current and
voltage readings are averaged before being displayed. It does not affect relay
PREFERENCES
DEFAULT MESSAGE
CYCLE TIME: 2.0 s
DEFAULT MESSAGE
TIMEOUT: 300 s
AVERAGE MOTOR
LOAD
TEMPERATURE DIS-
PLAY:
TRACE MEMORY
TRIGGER
TRACE MEMORY BUF-
FERS
DISPLAY UPDATE
INTERVAL: 0.4 s
MOTOR LOAD FILTER
INTERVAL: 0
Range: 0.5 to 10.0 s in steps of 1
Range: 10 to 900 s in steps of 1
Range: 1 to 90 min. in steps of 1
Range: Celsius, Fahrenheit
Range: 1 to 100% in steps of 1
Range:1x64, 2x42, 3x32, 4x35, 5x21,
6x18, 7x16, 8x14, 9x12, 10x11,
11x10, 12x9, 13x9, 14x8, 15x8,
16x7 cycles.
Range: 0.1 to 6.0 s in steps of 0.1
Range: 0 to 32 cycles (0 = OFF) in steps
of 1
5–9