A5 Event Recorder - GE Multilin 469 Instruction Manual

Motor management relay
Table of Contents

Advertisement

CHAPTER 6: ACTUAL VALUES
6.6

A5 Event Recorder

6.6.1
Event 01 to Event 256
01
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
PATH: ACTUAL VALUES
EVENT
[ ]
<Cause>
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
A5 EVENT RECORDER
EVENT 01(256)
TIME OF EVENT 01:
00:00:00.0
DATE OF EVENT 01:
Jan. 01, 1992
MOTOR SPEED DUR-
ING
TACHOMETER DURING
EVENT01: 0 RPM
A:
0
B:
0
C:
0
A
EVEN
MOTOR LOAD
EVENT01: 0.00 x
CURRENT UNBALANCE
EVENT01: 0%
GROUND CURRENT
EVENT01: 0.00 A
A:
0
B:
0
C:
0
A Diff.
HOTTEST STATOR
RTD:
HOTTEST BEARING
RTD:
HOTTEST OTHER
RTD:
AMBIENT
RTD:
Vab:
0
Vbc:
0
Vca:
0
A
EVE
Van:
0
Vbn:
0
Vcn:
0
A
EVE
SYSTEM FREQUENCY
EVENT01: 0.00 Hz
0
kW
0
kVA
Range: hour:minutes:seconds
Range: month day, year
Range: High Speed, Low Speed. Seen if
two-speed feature is enabled.
Range: 0 to 3600 RPM. Seen only if a
Digital Input is Tachometer.
Range: 0 to 100000 A
Range: 0.00 to 20.00 x FLA
Range: 0 to 100%
Range: 0.00 to 5000.0 A. Not seen if
Ground CT is set as None.
Range: 0 to 5000 A. Seen only if Phase
Differential CT is set.
Range: –50 to 250°C, --- (no RTD). Seen
if at least 1 RTD is set as Stator.
Range: –50 to 250°C, --- (no RTD). Seen
if at least 1 RTD is Bearing.
Range: –50 to 250°C, --- (no RTD). Seen
if at least 1 RTD is set as Other.
Range: –50 to 250°C, --- (no RTD). Seen
if at least 1 RTD is Ambient.
Range: 0 to 20000 A. Not seen if VT
Connection set as None
Range: 0 to 20000 A. Seen only if VT
Connection set as Wye.
Range: 0.00, 20.00 to 120.00 Hz. Not
seen if VT Connection is None.
Range: –50000 to 50000 kVA. Not seen
if VT Connection is set as None
6–33