6.3.8
Phasors
PHASORS
]
Note
6–16
MESSAGE
MESSAGE
The values for analog inputs are shown here. The name of the input and the units will
reflect those programmed for each input. If no analog inputs are programmed in
ANALOG I/O
ANALOG INPUT 1(4)
message will appear when an attempt is made to enter this group of messages.
PATH: ACTUAL VALUES
[
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The 469 Motor Management Relay was designed to display lagging angles. Therefore, if a
system condition would cause the current to lead the voltage by 45°, the 469 relay will
display such angle as 315° Lag instead of 45° Lead.
When the currents and voltages measured by the relay are zero, the angles displayed
by the relay and those shown by the EnerVista 469 Setup software are not fixed values.
The EnerVista 469 Setup software is a useful tool to view the vectors seen by the relay in
graphical format. The same information described above is displayed by the EnerVista 469
Setup software as follows:
ANALOG 3-4
0 Percent
ANALOG 3-4
0 Units
, the
THIS FEATURE NOT PROGRAMMED
A2 METERING DATA
PHASORS
Va PHASOR
0.0% AT 0°Lag
Vb PHASOR
0.0% AT 0°Lag
Vc PHASOR
0.0% AT 0°Lag
Ia PHASOR
0.0% AT 0°Lag
Ib PHASOR
0.0% AT 0°Lag
Ic PHASOR
0.0% AT 0°Lag
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 6: ACTUAL VALUES
Range: –5100 to 4900%. Seen only if
Analog In Diff 3-4 set to %Diff
Range: –100000 to 100000. Seen only
if Analog In Diff 3-4 is Abs Diff
S12
flash