5–106
SPEED2 TRIP AT
MESSAGE
3.00 x FLA: 43.7
SPEED2 TRIP AT
MESSAGE
3.25 x FLA: 36.6
SPEED2 TRIP AT
MESSAGE
3.50 x FLA: 31.1
SPEED2 TRIP AT
MESSAGE
3.75 x FLA: 26.8
SPEED2 TRIP AT
MESSAGE
4.00 x FLA: 23.2
SPEED2 TRIP AT
MESSAGE
4.25 x FLA: 20.5
SPEED2 TRIP AT
MESSAGE
4.50 x FLA: 18.2
SPEED2 TRIP AT
MESSAGE
4.75 x FLA: 16.2
SPEED2 TRIP AT
MESSAGE
5.00 x FLA: 14.6
SPEED2 TRIP AT
MESSAGE
5.50 x FLA: 12.0
SPEED2 TRIP AT
MESSAGE
6.00 x FLA: 10.0
SPEED2 TRIP AT
MESSAGE
6.50 x FLA: 8.5 s
SPEED2 TRIP AT
MESSAGE
7.00 x FLA: 7.3 s
SPEED2 TRIP AT
MESSAGE
7.50 x FLA: 6.3 s
SPEED2 TRIP AT
MESSAGE
8.00 x FLA: 5.6 s
SPEED2 TRIP AT
MESSAGE
10.0 x FLA: 5.6 s
SPEED2 TRIP AT
MESSAGE
15.0 x FLA: 5.6 s
SPEED2 TRIP AT
MESSAGE
20.0 x FLA: 5.6 s
SPEED2 MIN ALLOW-
MESSAGE
ABLE
SPEED2 ISTALL @
MESSAGE
MIN
SPEED2 SAFE STALL
MESSAGE
@
CHAPTER 5: SETTINGS
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 70 to 95% in steps of 1
Range: 2.00 to 15.00 x FLA in steps of
0.01
Range: 0.5 to 999.9 s in steps of 0.1