CHAPTER 5: SETTINGS

5.12.4 Pulse Output

PULSE
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
period. The average value of the buffer is calculated and stored as the new demand value
every minute. Demand for real and reactive power is only positive quantities (+kW and
+kvar).
Demand
where: N = programmed demand period in minutes
n = time in minutes.
160
140
120
100
80
60
40
20
0
t=0
t+10
FIGURE 5–19: Rolling Demand (15 Minute Window)
PATH: SETTINGS
S11 MONITORING
[
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
N
1
---
Average
=
N
N
n
1
=
t+20
t+30
t+40
t+50
t+60
TIME
PULSE OUTPUT
POS kWh PULSE
OUTPUT
POS kWh PULSE
OUTPUT
POS kvarh PULSE
OUT
POS kvarh PULSE
OUT
NEG kvarh PULSE
OUT
NEG kvarh PULSE
OUT
RUNNING TIME
PULSE
RUNNING TIME
PULSE
(EQ 5.12)
t+70
t+80
t+90 t+100
808717A1.CDR
Range: Off, Alarm, Auxiliary2,
Auxiliary3
Range: 1 to 50000 kWh in steps of 1
Range: Off, Alarm, Auxiliary2,
Auxiliary3
Range: 1 to 50000 kvarh in steps of 1
Range: Off, Alarm, Auxiliary2,
Auxiliary3
Range: 1 to 50000 kvarh in steps of 1
Range: Off, Alarm, Auxiliary2,
Auxiliary3
Range: 1 to 50000 s in steps of 1
5–89