5.10 S9 Voltage Elements

5.10.1 Undervoltage
UNDERVOLTAGE
5–76
PATH: SETTINGS
S9 VOLTAGE ELEM.
[
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The
U/V ACTIVE ONLY IF BUS ENERGIZED
or trips when the bus is not energized. If this settings is programmed to "Yes", at least one
voltage must be greater than 20% of the nominal nameplate voltage rating for any alarm/
trip. If the load is high inertia, it may be desirable to trip the motor off-line or prevent it from
starting in the event of a total loss of line voltage. Programming "No" for this settings
ensures that the motor is tripped and may be restarted only after the bus is re-energized.
UNDERVOLTAGE
U/V ACTIVE ONLY
IF
UNDERVOLTAGE
ALARM: Off
ASSIGN ALARM
RELAYS:
UNDERVOLTAGE
ALARM
STARTING U/V
ALARM
UNDERVOLTAGE
ALARM
UNDERVOLTAGE
ALARM
UNDERVOLTAGE
TRIP: Off
UNDERVOLTAGE TRIP
MODE: 1-Phase
ASSIGN TRIP
RELAYS:
UNDERVOLTAGE TRIP
PICKUP: 0.80 x
STARTING U/V TRIP
PICKUP: 0.80 x
UNDERVOLTAGE TRIP
DELAY: 3.0 s
settings may be used to prevent nuisance alarms
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
Range: No, Yes
Range: Off, Latched, Unlatched
Range: Alarm, Alarm & Auxiliary2,
Alarm & Aux2 & Aux3, Alarm &
Auxiliary3, Auxiliary2, Aux2 &
Aux3, Auxiliary3
Range: 0.60 to 0.99 x RATED in steps of
0.01
Range: 0.60 to 1.00 x RATED in steps of
0.01. Enter "1.00" to turn this
function off.
Range: 0.0 to 60.0 s in steps of 0.1
Range: On, Off
Range: Off, Latched, Unlatched
Range: 1-Phase, 3-Phase
Range: Trip, Trip & Auxiliary2, Trip &
Aux2 & Aux3, Trip & Auxiliary3
Range: 0.60 to 0.99 x RATED in steps of
0.01
Range: 0.60 to 1.00 x RATED in steps of
0.01. Enter "1.00" to turn this
function off.
Range: 0.0 to 60.0 s in steps of 0.1