Pressure Switch Alarm
PATH: SETTINGS
S3 DIGITAL INPUTS
[
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
These settings apply only if the
Once the pressure switch alarm function is chosen for one of the assignable digital inputs,
the settings messages shown here will follow the assignment message. The Pressure
Switch alarm feature may be blocked for a specified period of time from a motor start. A
value of zero for the block time indicates that the feature is always active, when the motor
is stopped or running. After the block delay has expired, the digital input will be monitored.
If a closure occurs, after the specified delay, an alarm will occur.
Pressure Switch Trip
PATH: SETTINGS
S3 DIGITAL INPUTS
[
MESSAGE
MESSAGE
MESSAGE
These settings apply only if the
Once the Pressure Switch Trip function is chosen for one of the digital inputs, the settings
messages shown here will follow the assignment message. The Pressure Switch Trip
feature may be blocked for a specified period of time from a motor start. A value of zero for
the Block time indicates that the feature is always active, when the motor is stopped or
running. After the block delay has expired, the digital input will be monitored. If a closure
occurs, after the specified delay, a trip will occur.
ASSIGNABLE INPUT 1(4)
INPUT 1 FUNCTION:
Pressure Sw Alarm
BLOCK PRES. SW.
ALARM
PRESSURE SWITCH
ALARM: Unlatched
ASSIGN ALARM
RELAYS:
PRESSURE SW.
ALARM
PRESSURE SW.
ALARM
is "Pressure Sw. Alarm".
INPUT 1(4) FUNCTION
ASSIGNABLE INPUT 1(4)
INPUT 1 FUNCTION:
Pressure Switch
BLOCK PRES. SW.
TRIP
ASSIGN TRIP
RELAYS:
PRESSURE SW. TRIP
DELAY: 5.0 s
is "Pressure Switch Trip".
INPUT 1(4) FUNCTION
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
Range: See above
Range: 0 to 5000 s in steps of 1
Range: Latched, Unlatched
Range: Alarm, Alarm & Auxiliary2,
Alarm & Auxiliary2 & Aux3,
Alarm & Auxiliary3, Auxiliary2,
Aux2 & Aux3, Auxiliary3
Range: 0.1 to 100.0 sec., step: 0.1
Range: On, Off
Range: See above
Range: 0 to 5000 sec.; step: 1
Range: Trip, Trip & Auxiliary2, Trip &
Aux2 & Aux3, Trip & Auxiliary3
Range: 0.1 to 100.0 s in steps of 0.1