The 469 measures motor demand for several parameters (current, kW, kvar, and kVA).
These values may be of interest for energy management programs where processes may
be altered or scheduled to reduce overall demand on a feeder.
Demand is calculated as follows. Every minute, an average magnitude is calculated for
current, +kW, +kvar, and kVA based on samples taken every 5 seconds. These values are
stored in a FIFO (first in, first out) buffer. The buffer size is dictated by the settings demand
CURRENT DEMAND
ALARM EVENTS: Off
kW DEMAND
PERIOD: 15 min.
kW DEMAND
ALARM: Off
ASSIGN ALARM
RELAYS:
kW DEMAND
LIMIT: 100 kW
kW DEMAND
ALARM EVENTS: Off
kvar DEMAND
PERIOD: 15 min.
kvar DEMAND
ALARM: Off
ASSIGN ALARM
RELAYS:
kvar DEMAND
LIMIT: 100 kvar
kvar DEMAND
ALARM EVENTS: Off
kVA DEMAND
PERIOD: 15 min.
kVA DEMAND
ALARM: Off
ASSIGN ALARM
RELAYS:
kVA DEMAND
LIMIT: 100 kVA
kVA DEMAND
ALARM EVENTS: Off
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
Range: On, Off
Range: 5 to 90 min. in steps of 1
Range: Off, Latched, Unlatched
Range: Alarm, Alarm & Auxiliary2,
Alarm & Aux2 & Aux3, Alarm &
Auxiliary3, Auxiliary2, Aux2 &
Aux3, Auxiliary3
Range: 1 to 50000 kW in steps of 1
Range: On, Off
Range: 5 to 90 min. in steps of 1
Range: Off, Latched, Unlatched
Range: Alarm, Alarm & Auxiliary2,
Alarm & Aux2 & Aux3, Alarm &
Auxiliary3, Auxiliary2, Aux2 &
Aux3, Auxiliary3
Range: 1 to 50000 kvar, step 1
Range: On, Off
Range: 5 to 90 min. in steps of 1
Range: Off, Latched, Unlatched
Range: Alarm, Alarm & Auxiliary2,
Alarm & Aux2 & Aux3, Alarm &
Auxiliary3, Auxiliary2, Aux2 &
Aux3, Auxiliary3
Range: 1 to 50000 kVA, step: 1