CHAPTER 7: TESTING
7.2

Hardware Functional Testing

7.2.1
Phase Current Accuracy Test
7.2.2
Voltage Input Accuracy Test
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
The 469 specification for phase current accuracy is ±0.5% of 2 × CT when the injected
current is less than 2 × CT. Perform the steps below to verify accuracy.
Alter the following settings:
S2 SYSTEM SETUP
Measured values should be ±10 A.
Inject the values shown in the table below.
Verify accuracy of the measured values.
View the measured values in:
INJECTED
INJECTED
CURRENT
CURRENT
1 A UNIT
5 A UNIT
0.1 A
0.5 A
0.2 A
1.0 A
0.5 A
2.5 A
1.0 A
5.0 A
1.5 A
7.5 A
2.0 A
10 A
The 469 specification for voltage input accuracy is ±0.5% of full scale (273 V). Perform the
steps below to verify accuracy.
Alter the following settings:
S2 SYSTEM SETUP
S2 SYSTEM SETUP
Measured values should be ±13.65 V.
Apply the voltage values shown in the table.
Verify accuracy of the measured values.
View the measured values in:
APPLIED
EXPECTED
LINE-NEUTRAL
VOLTAGE
VOLTAGE
READING
30 V
300 V
50 V
500 V
100 V
1000 V
150 V
1500 V
CURRENT SENSING
PHASE CT PRIMARY:
A2 METERING DATA
CURRENT METERING
EXPECTED
MEASURED
CURRENT
CURRENT
READING
PHASE A
100 A
200 A
500 A
1000 A
1500 A
2000 A
VOLTAGE SENSING
VT CONNECTION TYPE:
VOLTAGE SENSING
VOLTAGE TRANSFORMER RATIO:
A2 METERING DATA
VOLTAGE METERING
MEASURED
VOLTAGE A-N
"1000 A"
MEASURED
MEASURED
CURRENT
CURRENT
PHASE B
PHASE C
"Wye"
"10.00:1"
MEASURED
MEASURED
VOLTAGE B-N
VOLTAGE C-N
7–3