CHAPTER 5: SETTINGS
SPEED2
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
Refer to Custom Overload Curve on page 5–43 for additional details on the custom
overload curves available for Speed2.
•
Voltage Dependent Overload Curves
If the
SELECT CURVE STYLE
following settings will appear:
PATH: SETTINGS
S14 2-SPEED MOTOR
[
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
SPEED2 TRIP AT
7.50 x FLA: 6.3 s
SPEED2 TRIP AT
8.00 x FLA: 5.6 s
SPEED2 TRIP AT
10.0 x FLA: 5.6 s
SPEED2 TRIP AT
15.0 x FLA: 5.6 s
SPEED2 TRIP AT
20.0 x FLA: 5.6 s
is set to "Voltage Dependent" in the Thermal Model, the
SPEED2 OVERLOAD SETUP
SPEED2 TRIP AT
1.01 x FLA:
SPEED2 TRIP AT
1.05 x FLA:
SPEED2 TRIP AT
1.10 x FLA:
SPEED2 TRIP AT
1.20 x FLA: 795.4
SPEED2 TRIP AT
1.30 x FLA: 507.2
SPEED2 TRIP AT
1.40 x FLA: 364.6
SPEED2 TRIP AT
1.50 x FLA: 280.0
SPEED2 TRIP AT
1.75 x FLA: 169.7
SPEED2 TRIP AT
2.00 x FLA: 116.6
SPEED2 TRIP AT
2.25 x FLA: 86.1
SPEED2 TRIP AT
2.50 x FLA: 66.6
SPEED2 TRIP AT
2.75 x FLA: 53.3
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
5–105