CHAPTER 5: SETTINGS
SPEED2
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
Refer to Custom Overload Curve on page 5–43 for additional details on the custom
overload curves available for Speed2.
Voltage Dependent Overload Curves
If the
SELECT CURVE STYLE
following settings will appear:
PATH: SETTINGS
S14 2-SPEED MOTOR
[
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
SPEED2 TRIP AT
7.50 x FLA: 6.3 s
SPEED2 TRIP AT
8.00 x FLA: 5.6 s
SPEED2 TRIP AT
10.0 x FLA: 5.6 s
SPEED2 TRIP AT
15.0 x FLA: 5.6 s
SPEED2 TRIP AT
20.0 x FLA: 5.6 s
is set to "Voltage Dependent" in the Thermal Model, the
SPEED2 OVERLOAD SETUP
SPEED2 TRIP AT
1.01 x FLA:
SPEED2 TRIP AT
1.05 x FLA:
SPEED2 TRIP AT
1.10 x FLA:
SPEED2 TRIP AT
1.20 x FLA: 795.4
SPEED2 TRIP AT
1.30 x FLA: 507.2
SPEED2 TRIP AT
1.40 x FLA: 364.6
SPEED2 TRIP AT
1.50 x FLA: 280.0
SPEED2 TRIP AT
1.75 x FLA: 169.7
SPEED2 TRIP AT
2.00 x FLA: 116.6
SPEED2 TRIP AT
2.25 x FLA: 86.1
SPEED2 TRIP AT
2.50 x FLA: 66.6
SPEED2 TRIP AT
2.75 x FLA: 53.3
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1