5.14.6 Comm Port Monitor

COMMUNICATION
5.14.7 GE Multilin Use Only
MULTILIN
5–102
PATH: SETTINGS
S13 469 TESTING
[
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
During the course of troubleshooting communications problems, it can be very useful to
see the data that is first being transmitted to the 469 from some master device, and then
see the data that the 469 transmits back to that master device. The messages shown here
should make it possible to view that data. Any of the three communications ports may be
monitored. After the communication buffers have been cleared, any data received from
the communications port being monitored will be stored in the Rx1 and Rx2 buffers with '//
' acting as a character break between messages. If the 469 transmits a message, it will
appear in the Tx1 and Tx2 buffers. In addition to these buffers, there is a message that will
indicate the status of the last received message.
PATH: SETTINGS
S13 469 TESTING
GE
[ ]
This section is for use by GE Multilin personnel for testing and calibration purposes.
COMMUNICATION PORT MONITOR
MONITOR COMM.
PORT:
CLEAR COMM.
BUFFERS: No
LAST Rx BUFFER:
Received OK
Rx1:
02,03,00,67,00,
Rx2: ------------
----
Tx1:
02,03,06,00,64,
Tx2: ------------
----
GE MULTILIN USE ONLY
GE MULTILIN USE
ONLY
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
Range: Computer RS485, Auxiliary
RS485, Front Panel RS232
Range: No, Yes
Range: Buffer Cleared, Received OK,
Wrong Slave Addr., Illegal
Function, Illegal Count, Illegal
Reg. Addr., CRC Error, Illegal
Data
Range: received data in HEX
Range: received data in HEX
Range: transmitted data in HEX
Range: transmitted data in HEX
Range: N/A