5.14.3 Fault Setup
FAULT
5–100
PATH: SETTINGS
S13 469 TESTING
[
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The values entered under Fault Values will be substituted for the measured values in the
469 when the simulation mode is "Simulate Fault".
FAULT SETUP
FAULT CURRENT
PHASE A: 0.00 x
FAULT CURRENT
PHASE B: 0.00 x
FAULT CURRENT
PHASE C: 0.00 x
FAULT GROUND
CURRENT: 0.0 A
FAULT VOLTAGES
VLINE: 1.00 x
FAULT CURRENT
LAGS VOLTAGE: 0°
FAULT DIFF AMPS
IDIFF: 0.00 x CT
FAULT STATOR
RTD TEMP: 40°C
FAULT BEARING
RTD TEMP: 40°C
FAULT OTHER
RTD TEMP: 40°C
FAULT AMBIENT
RTD TEMP: 40°C
FAULT SYSTEM
FREQUENCY: 60.0
FAULT ANALOG
INPUT 1: 0%
FAULT ANALOG
INPUT 2: 0%
FAULT ANALOG
INPUT 3: 0%
FAULT ANALOG
INPUT 4: 0%
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
Range: 0.00 to 20.00 x CT in steps of
0.01
Range: 0.00 to 20.00 x CT in steps of
0.01
Range: 0.00 to 20.00 x CT in steps of
0.01
Range: 0.0 to 5000.0 A in steps of 0.1
Range: 0.00 to 1.10 x RATED in steps of
0.01
Range: 0 to 359° in steps of 1
Range: 0.00 to 1.10 x RATED in steps of
0.01
Range: –50 to 250°C in steps of 1
Range: –50 to 250°C in steps of 1
Range: –50 to 250°C in steps of 1
Range: –50 to 250°C in steps of 1
Range: 45.0 to 70.0 Hz in steps of 0.1
Range: 0 to 100% in steps of 1
Range: 0 to 100% in steps of 1
Range: 0 to 100% in steps of 1
Range: 0 to 100% in steps of 1