Lenze 9215 Operating Instructions Manual page 72

9200 series servo controller
Table of Contents

Advertisement

Code Name
C117* Assignment of
C125* Baud rate
C140* Enable encoder
C153* Minimum limit
C154* Maximum limit
C158* Actual following
C159* Homing OK
68
Parameter
-0-
Qmin terminal
-1-
-2-
-0-
-1-
-2-
-3-
-0-
setting
-1-
0
monitor 1
3000
monitor 1
xxxx
error
-0-
-1-
Terminal X5,42 has the function:
Qmin
Terminals X5,42 has the function:
following error limit reached
If code C117 is set to -1-, the terminal
X5,42 changes from HIGH to LOW
level as soon as reaching the
following error limit C255.
Terminal X5,42 has the function:
controller enable.
If code C117 is set to -2- the High
level of terminal X5,42 displays an
pulse enable of the rectifier.
Note: If the function pulse enable is
assigned to terminal X5,42 to control
a mechanical brake please note that
you set Code117 to -2- before
controlling the brake. The loading of
the factory setting deactivates this
function.
9600 baud
4800 baud
2400 baud
1200 baud
C027 active
C028 active
Setting range: 0 rpm...C154
Step:
1 rpm
Setting of the minimum limit to give
the speed to monitor output 1.
Speeds, the absolute number of
which is smaller than the minimum
limit, generate 0 V on the monitor
output 1 of terminal 62.
Setting range: C153...9000 rpm
Step:
1 rpm
Corresponds to an output voltage of
10 V at terminal 62. Speeds > C154
generate a 10 V level on the monitor
output.
Display range: -3188...3188
increments
Step:
1 increment
Homing not finished
Homing successfully finished
The status -1- can also be set.
Therefore it is possible after mains
connection to start without homing, in
the homing mode (C250 = 1) with
Dig.-Set operation. The angular offset
C252 is then set to 0.
Accept-
see
ance
page
SH+PRG
SH+PRG
46
ON-LINE
ON-LINE
read only
SH+PRG


Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

921292229217922492259226 ... Show all

Table of Contents