Eaton UPS Sidecar Powerware 9390 Installation And Operation Manual page 68

Powerware corporation powerware 9390 ups sidecar installation and operation manual
Hide thumbs Also See for UPS Sidecar Powerware 9390:
Table of Contents

Advertisement

INSTALLATION INFORMATION
Basic Unit Rating
Input and Bypass Input
Output
AC Input to Maintenance
Bypass (without BIB or RIB, or
dual feed with BIB and RIB)
(3) Phases, (1) Neutral--- if required,
(1) Ground
Minimum Conductor Size
Number per Phase
AC Input to Maintenance
Bypass (single feed with BIB, or
single feed with BIB and RIB)
(3) Phases, (1) Neutral--- if required,
(1) Ground
Minimum Conductor Size
Number per Phase
AC Input to Optional RIB
(3) Phases, (1) Ground
Minimum Conductor Size
Number per Phase
AC Output to Critical Load
Full Load Current
(3) Phases, (1) Neutral--- if required,
(1) Ground
Minimum Conductor Size
Number per Phase
NOTE Callout letters
A-18
EATON Powerware
Table C
INPUT/OUTPUT Ratings & External Wiring Requirements for
.
Powerware 9390 UPS Sidecar (Maintenance Bypass) 480/480V
Units
UPS kVA
VOLTS
VOLTS
AMPS
A
AWG or kcmil
(each)
AMPS
A
AWG or kcmil
(each)
AMPS
B
AWG or kcmil
(each)
AMPS
C
AWG or kcmil
(each)
A, B,
and
2 of 11, 3 of 11, 4 of 11, 5 of 11, 6 of 11, 7 of 11, 8 of 11, and 9 of 11.
®
9390 UPS Sidecar Installation and Operation Manual
Rating 50/60 Hz
20
30
40
50
480
480
480
480
480
480
480
480
24
36
48
60
6
4
4
2
(1)
(1)
(1)
(1)
30
40
55
67
6
4
4
2
(1)
(1)
(1)
(1)
30
40
55
67
6
4
4
2
(1)
(1)
(1)
(1)
24
36
48
60
6
4
4
2
(1)
(1)
(1)
(1)
C
map to drawing 164201546 ---3, sheets 1 of 11,
DESCRIPTION:
POWER WIRING INSTALLATION NOTES
DRAWING NO:
164201546---4
REVISION:
D
S
164201586 Rev E www.powerware.com
60
80
100
120
480
480
480
480
480
480
480
480
72
96
120
144
1
1/0
4/0
4/0
(1)
(1)
(1)
(1)
80
105
130
160
1
1/0
4/0
4/0
(1)
(1)
(1)
(1)
80
105
130
160
1
1/0
4/0
4/0
(1)
(1)
(1)
(1)
72
96
120
144
1
1/0
4/0
4/0
(1)
(1)
(1)
(1)
SHEET:
2 of 10
DATE:
061507
160
480
480
193
1/0
(2)
210
1/0
(2)
210
1/0
(2)
193
1/0
(2)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Powerware 9390 ups sidecarPowerware series9390

Table of Contents