Eaton UPS Sidecar Powerware 9390 Installation And Operation Manual page 59

Powerware corporation powerware 9390 ups sidecar installation and operation manual
Hide thumbs Also See for UPS Sidecar Powerware 9390:
Table of Contents

Advertisement

AC INPUT
TO UPS
E1, E2, E3
K1
BATTERY
CONVERTER
E4. E5
Powerware 9390 UPS CABINET
SERIAL NUMBER SEVENTH
DIGIT AT "B" OR HIGHER
NOTE
1. A minimum of two separate feeds with
upstream feeder breakers, or one feed
with two upstream feeder breakers, must
be provided: one for the UPS and one for
the UPS Sidecar bypass input. DO NOT
use one feed or a single feeder breaker to
supply both the UPS and the UPS
.
Sidecar
2. Move bypass contactor wires to
bypass terminals for dual-feed.
3. If the load requires a neutral, a bypass
neutral feeder must be supplied.
EATON Powerware
E6, E7,
(SEE NOTE 2
E8, E12
DUAL-FEED)
K5
RECTIFIER
INVERTER
K3
MAINTENANCE BYPASS CONFIGURATION
160/100, 160/120, AND 160/160 kVA, 480/480V
WITH UPS SERIAL NUMBER SEVENTH DIGIT
DESCRIPTION:
DRAWING NO:
REVISION:
®
9390 UPS Sidecar Installation and Operation Manual
AC INPUT
TO BYPASS
A
E6, E7, E8
MAINTENANCE
BYPASS SWITCH
(MBP)
MAINTENANCE
ISOLATION SWITCH
(MIS)
UPS Sidecar
AT "B" OR HIGHER
UPS SIDECAR ONELINE DRAWINGS
164201546---3
DATE:
B
S
164201586 Rev E www.powerware.com
INSTALLATION INFORMATION
C
AC OUTPUT
TO
E9, E10, E11
CRITICAL LOAD
SHEET:
4 of 11
062806
A-9