INSTALLATION INFORMATION
BATTERY
CABINET
BATTERY
BREAKER
A ---
AC Input to UPS Rectifier (dual-feed)
B ---
AC Input to UPS Rectifier (single-feed) and Bypass (single- and dual-feed)
C ---
DC Input from Battery
D ---
Output to Critical Load
* ---
Overcurrent Protection Provided by Others
NOTE
1. UPM and system bypass input feeds
must come from the same source.
2. Remove jumper for dual-feed.
3. If the load requires a neutral, a bypass
neutral feeder must be supplied.
A-16
EATON Powerware
A
B
*
*
UPM 1
E1
E6
E2
E7
E3
E8
SEE NOTE 2
E12
K5
K1
FUSE
FUSE
RECTIFIER
STATIC
SWITCH
BATTERY
CONVERTER
INVERTER
FUSE
K3
C
E4. E5
TYPICAL PARALLEL REDUNDANT SYSTEM
(1+1 CONFIGURATION)
®
9390 UPS Sidecar Installation and Operation Manual
A
*
UPS Sidecar
E1
E2
E3
MOB 2
MOB 1
SLB
(OPTIONAL)
E9, E10, E11
D
OUTPUT TO
CRITICAL LOAD
DESCRIPTION:
UPS SIDECAR ONELINE DRAWINGS
DRAWING NO:
164201546---3
REVISION:
A
S
164201586 Rev E www.powerware.com
B
*
UPM 2
BATTERY
E6
CABINET
E7
E8
SEE NOTE 2
E12
K5
K1
FUSE
FUSE
RECTIFIER
STATIC
SWITCH
BATTERY
CONVERTER
INVERTER
FUSE
K3
C
E4. E5
BATTERY
BREAKER
SHEET:
DATE:
031505
11 of 11