CHAPTER 5: SETTINGS
Y LV
SRC 1
Phase CT
M1
Ground CT
M1
Phase VT
M5
Aux VT
None
5.5.4 87L power system
5.5.4.1 Menu
SETTINGS SYSTEM SETUP 87L POWER SYSTEM
87L POWER SYSTEM
L30 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
Figure 5-52: Example of use of sources
D HV
AUX
SRC 2
SRC 3
F1+F5
None
None
None
None
None
None
U1
NUMBER OF TERMINALS:
2
NUMBER OF CHANNELS:
1
CHARGING CURRENT
COMPENSATN: Disabled
POS SEQ CAPACITIVE
REACTANCE: 0.100 kΩ
Range: 2, 3
Range: 1, 2
Range: Disabled, Enabled
Range: 0.100 to 65.535 kΩin steps of 0.001
SYSTEM SETUP
5
5-123