SPECIFICATIONS
Sensing current:
Range:
Accuracy:
Isolation:
IRIG-B INPUT
IRIG formats accepted:
IRIG control bits:
2
Amplitude modulation:
DC shift:
Input impedance:
Isolation:

2.6.6 Power supply

LOW RANGE
Nominal DC voltage:
Minimum DC voltage:
Maximum DC voltage:
Voltage loss hold-up:
NOTE: Low range is DC only.
HIGH RANGE
Nominal DC voltage:
Minimum DC voltage:
Maximum DC voltage:
Nominal AC voltage:
Minimum AC voltage:
Maximum AC voltage:
Voltage loss hold-up:
ALL RANGES
Volt withstand:
Power consumption:
INTERNAL FUSE
Ratings:
Low range power supply:
High range power supply:
Interrupting capacity:
AC:
DC:

2.6.7 Outputs

FORM-A RELAY
Make and carry for 0.2 s:
Carry continuous:
2-36
5 mA
–50 to +250°C
±2°C
36 V pk-pk
B000...B007, B120...B127
IEEE Std C37.118.1-2011
1 to 10 V pk-pk
TTL–Compatible
50 kΩ
2 kV
24 to 48 V
20 V
75 V for SL power supply module
200 ms duration at maximum load
125 to 250 V
88 V
300 V
100 to 240 V at 50/60 Hz
88 V at 25 to 100 Hz
265 V at 25 to 100 Hz
200 ms duration at maximum load
2 × Highest Nominal Voltage for 10 ms
typical = 15 to 20 W/VA
maximum = 45 W/VA
contact factory for exact order code consumption
8 A / 250 V
4 A / 250 V
100 000 A RMS symmetrical
10 000 A
30 A as per ANSI C37.90
6 A
L30 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL