GE L30 Instruction Manual page 368

Line current differential system
Hide thumbs Also See for L30:
Table of Contents

Advertisement

GROUPED ELEMENTS
CURRENT DIFF SIGNAL SOURCE 1
current. If more than one source is configured, the other source currents are scaled to the CT with the maximum primary
current assigned by the
mandatory and is assigned with the
5
CURRENT DIFF BLOCK
CURRENT DIFF PICKUP
CURRENT DIFF CT TAP 1, 2
CT ratio to the local ratio if the CT ratios for the local and remote terminals differ. In two-terminal, two-channel applications
use the same value for both TAP 1 and TAP 2 settings, and in three-terminals accordingly remote 1 and 2 CTs. The setting
value is determined by CT
as the CT primary rated current). Ratio matching must always be performed against the remote CT with the maximum CT
primary defined by the
Differential Settings example in the Application of Settings chapter for details.
When an in-zone power transformer is present, calculate and use this setting by taking into account the in-zone power
transformer as follows.
In this equation, V
prim_rem
primary nominal voltage of the transformer winding at the local terminal.
CURRENT DIFF RESTRAINT 1, 2
CURRENT DIFF BREAK PT
INRUSH INHIBIT MODE
conditions. Modern transformers can produce small second harmonic ratios during inrush conditions. This can result in
undesired tripping of the protected line. Reducing the second harmonic inhibit threshold can jeopardize dependability and
speed of differential protection. When low, the second harmonic ratio causes problems in one phase only. This can be
utilized to ensure security by applying cross-phase blocking rather than lowering the inrush inhibit threshold.
If set to "Disabled", no inrush inhibit action is taken.
If set to "Per phase", the L30 performs inrush inhibit individually in each phase.
5-190
INRUSH INHIBIT
LEVEL: 20% fo
CURRENT DIFF GND
FUNCTION: Disabled
CURRENT DIFF GND
PICKUP: 0.10 pu
CURRENT DIFF GND
RESTRAINT: 25%
CURRENT DIFF GND
DELAY: 0.10 s
CURRENT DIFF DTT:
Enabled
CURRENT DIFF KEY DTT:
Off
CURRENT DIFF
TARGET: Self-reset
CURRENT DIFF
EVENTS: Disabled
— This setting selects the first source for the current differential element local operating
CURRENT DIFF SIGNAL SOURCE 1
SYSTEM SETUP  SIGNAL SOURCES  SOURCE 1
— This setting selects a FlexLogic operand to block the operation of the current differential element.
— This setting is used to select the current differential pickup value.
— These settings adapt the remote terminal 1 or 2 (communication channel 1 and 2 respectively)
/ CT
for local and remote terminal CTs (where CT
prim_rem
prim_loc
CURRENT DIFF SIGNAL SOURCE 1
is primary nominal voltage of the transformer winding at the remote terminal and V
— These settings select the bias characteristic for the first and second slope, respectively.
— This setting is used to select an intersection point between the two slopes.
— This setting selects the mode for blocking differential protection during magnetizing inrush
Range: 1.0 to 40.0% f
Range: Disabled, Enabled
Range: 0.05 to 1.00 pu in steps of 0.01
Range: 1 to 50% in steps of 1
Range: 0.00 to 5.00 s in steps of 0.01
Range: Disabled, Enabled
Range: FlexLogic operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
to
CURRENT DIFF SIGNAL SOURCE 4
menu.
through
CURRENT DIFF SIGNAL SOURCE 4
L30 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
in steps of 0.1
0
settings. This source is
/ CT
is referred to
prim_rem
prim_loc
settings. See the Current
Eq. 5-13
is
prim_loc