Line current differential system
Hide thumbs Also See for L30:
Table of Contents

Advertisement

TARGETS MENU
FAIL FUNCTION" setting enables/disables this self test. The target for this self test is priority-based, with the third one
being the highest priority. For example, if all three SFP modules fail, then the third SFP target is activated. If the third
SFP module failure resolves, then the second SFP target is activated.
AUTHENTICATION FAIL
Latched target message: No.
Description of problem: The number of failures threshold was exceeded.
What to do: Wait for the lockout interval and try to authenticate again.
FIRMWARE LOCK
Message: "Unauthorized firmware attempt"
Latched target message: No.
Description of problem: A firmware upgrade operation was attempted while the lock relay setting was enabled.
What to do: Ask the Supervisor to unlock the relay and try again.
SETTING LOCK
Message: "Unauthorized setting write"
Latched target message: No.
Description of problem: A setting write was attempted while the lock relay setting was enabled.
What to do: Ask the Supervisor to unlock the settings and try again.
SERVER UNAVAILABLE
Message: "An attempt to contact the Radius server has failed"
Latched target message: No.
Description of problem: The RADIUS authentication server is unavailable.
What to do: Verify network connectivity and try again.
7
DOS PARTITION ALARM:
SELF-TEST ERROR
Description of problem: There is a problem with the Compact Flash memory in the CPU module.
How often the test is performed: On relay power-up and afterwards once every 24 hours.
What to do: Contact the factory.
PROTOTYPE FIRMWARE:
Self Test Error
Description of problem: Seen until the builds is tagged as being 'release candidate' or 'gold' builds.
What to do: Update firmware to either of these builds.
7.2.2.4 HardFiber self-test error messages
In addition to those provided by the standard UR-series devices, the UR devices implement HardFiber self-tests. These are
listed here. Any abnormal diagnostic condition indicated by the LEDs or the critical failure relay also results in a self-test
message, so troubleshooting is described here. For other relays, such at the B95
7-12
CHAPTER 7: COMMANDS AND TARGETS
Plus
, see that product's instruction manual.