GE L30 Instruction Manual page 223

Line current differential system
Hide thumbs Also See for L30:
Table of Contents

Advertisement

CHAPTER 5: SETTINGS
PRODUCT SETUP
IEC 61850 protocol configuration settings are accessed through software panels that are selected either in the Online
Window area (see figure) or the Offline Window area in the EnerVista software.
The EnerVista software also includes an interface that is compatible with firmware versions 5.0 to 7.2 to configure
subscribers. Use the Simplified GOOSE Configurator in the Offline Window area.
Figure 5-10: IEC 61850 protocol panel in EnerVista software
5
The IEC 61850 window is divided into a navigation pane on the left and a settings panel on the right. You expand and click
an option on the left to display its panel on the right. The following figure shows an example for Server Configuration. The
SETTING column contains the names of the settings, and the PARAMETER column is used to enter the settings. Hovering
the mouse over a setting name displays a tool-tip showing the 61850 information model name of the setting or its location
in SCL files.
Figure 5-11: IEC 61850 panel
Opening the IEC 61850 window while online causes the UR Setup software to retrieve and import an SCL file from the L30.
This System Configuration Description (SCD) file contains all the settings in the UR at the time of the file request, both those
that are mapped into the IEC 61850 information model (that is, the "public" sections) and those that are not in the model
L30 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
5-45

Hide quick links:

Advertisement

Table of Contents
loading