GE L30 Instruction Manual page 341

Line current differential system
Hide thumbs Also See for L30:
Table of Contents

Advertisement

CHAPTER 5: SETTINGS
Operand type
as above
as above
as above
as above
SETTINGS  SYSTEM SETUP  PHASOR MEASUREMENT UNIT  PMU AGGREGATOR 1  90-5 AGGR 1
CONFIGURATION
 90-5 AGGR 1
 CONFIGURATION
— A user-defined visible string of characters (max. 56) to identify the source of the stream. This
PMU AGGREGATOR 1 NAME
value, concatenated with the Aggregator IDCode and Aggregator Class of Service, is mapped into the IEC 61850 MSVID
filed in the output stream.
AGGREGATOR 1: PHYSICAL PORT
transmitted. The range is 1, 2, 3.
PMU AGGREGATOR 1: UDP PORT
A default setting value for IEC 6150-90-5 is provided.
PMU AGGREGATOR 1: NUMBER OF ASDUs
through to 4.
Table 5-20: Number of ASDUs
Settings for
Transmission
ASDU
1
ASDU at T0 (current values)
2
ASDU at T-1 (previous values) + ASDU at T0 (current values)
3
ASDU at T-2 (previous values) + ASDU at T-1 (previous values) + ASDU at T0 (current values)
4
ASDU at T-3 (previous values) + ASDU at T-2 (previous values) + ASDU at T-1 (previous values) + ASDU at T0 (current values)
5.5.8.20 Control blocks
SETTINGS  SYSTEM SETUP  PHASOR MEASUREMENT UNIT  90–5 R-SV CB 1 CONFIGURATION
 90-5 R-SV CB 1
 CONFIGURATION
L30 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
Operand syntax
AGTR2 PDC CNTRL 1
AGTR2 PDC CNTRL 2
AGTR2 PDC CNTRL 3
AGTR1 PDC CNTRL 16
PMU AGGREGATOR 1
NAME:
PMU AGGREGATOR 1
PORT: 1
PMU AGGREGATOR 1
UDP PORT: 102
PMU AGGREGATOR 1
NUMBER OF ASDUs: 1
— This setting determines the physical ports through which the synchrophasor traffic is
— This setting selects the UDP port number that is used by this dataset for network reporting.
— This setting sets the number of Application Service Data Units (ASDUs) from 1
R-SV CB1 SVENA:
Off
R-SV CB1 CLIENT CTRL:
Off
R-SV CB1 SVENA DFLT:
Off
R-SV CB1 CONFREV:
1
Operand description
Phasor data concentrator asserts control bit 1 as
received via the network
Phasor data concentrator asserts control bit 2 as
received via the network
Phasor data concentrator asserts control bit 3 as
received via the network
Phasor data concentrator asserts control bit 16, as
received via the network
Range: 56-character ASCII text (blank by default)
Range: 1, 2, 3
Range: 0 to 65534 in steps of 1
Range: 1 to 4
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: 1 to 4294967295
SYSTEM SETUP
5
5-163

Hide quick links:

Advertisement

Table of Contents
loading