Upgrade Software - GE L30 Instruction Manual

Line current differential system
Hide thumbs Also See for L30:
Table of Contents

Advertisement

CHAPTER 11: MAINTENANCE
To restore the list of sites and devices from an Environment backup:
1.
In EnerVista, click File > Environment > Restore. A window opens.
2.
Select the .ENV file to restore.

11.7 Upgrade software

In general, the latest releases of the EnerVista software can be used with all firmware versions, for example EnerVista
software released for UR 7.4 can be used to access multiple UR devices that have version 7.4x, 7.2x, and 6.0x firmware
installed.
Existing installations do not need to be uninstalled before upgrade.
You can also downgrade the software; use the same procedure.
To upgrade the EnerVista software:
1.
If a beta version of the EnerVista UR Setup software is installed, uninstall it, for example using the Windows Control
Panel.
2.
Download the latest EnerVista software and/or firmware from
http://www.gegridsolutions.com/app/ViewFiles.aspx?prod=urfamily&type=7
3.
Double-click the file and complete the wizard. The software installs.
4.
Access the software and check the version number under Help > About. If the new version does not display, try
uninstalling the software and reinstalling the new versions.
A message can display about a version not being supported. An example is when upgrading from version 7.12K to 7.4x.
The 7.12K entry is removed from the Offline Window area.
A message can display in the EnerVista software upon launch that "a device from the environment was not recognized."
This means that a device is online and its firmware version conflicts with the software version. In the example shown, a
C60 with firmware version 7.5x is online, but the software version is 7.3x. Updating removed incompatible files and
changed the device to version 7.3x, after which you need to make the order codes consistent as outlined next.
Figure 11-9: Mismatch in order code between software and device
To make the order codes consistent:
1.
In EnerVista, click the Device Setup button. The window opens.
2.
Expand the entry for the UR device.
3.
Click the Read Order Code button. The order code and version of the device are populated to the software.
4.
Click the OK button to save the change.
L30 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
UPGRADE SOFTWARE
11
11-11

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents