Trip Decision Example; Trip Decision Test - GE L30 Instruction Manual

Line current differential system
Hide thumbs Also See for L30:
Table of Contents

Advertisement

CHAPTER 10: THEORY OF OPERATION

10.2.2 Trip decision example

Assume the following settings:
Slope 1: S
= 10%
1
Slope 2: S
= 10%
2
Breakpoint: BP = 5 pu secondary
Pickup: P = 0.5 pu
Assume the following local and remote currents:
= 4.0 pu ∠0°
Local current: I
local
Remote current: I
= 0.8 pu ∠180°
remote
The assumed condition is a radial line with a high resistance fault, with the source at the local end only, and through a
resistive load current. The operating current is:
Since the current at both ends is less than the breakpoint value of 5.0, the equation for two-terminal mode is used to
calculate restraint as follows:
where σ = 0, assuming a pure sine wave.

10.2.3 Trip decision test

The trip condition is shown.
The use of the
CURRENT DIFF PICKUP
settings are discussed in the Current Differential section of the Settings chapter.
The following figure shows how the L30 settings affect the restraint characteristics. The local and remote currents are 180°
apart, which represents an external fault. The breakpoint between the two slopes indicates the point where the restraint
area is becoming wider to override uncertainties from CT saturation, fault noise, harmonics, and so on. Increasing the
slope percentage increases the width of the restraint area.
L30 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
,
,
CURRENT DIFF RESTRAINT 1
CURRENT DIFF RESTRAINT 2
OPERATING CONDITION CHARACTERISTICS
, and
CURRENT DIFF BREAK PT
Eq. 10-34
Eq. 10-35
Eq. 10-36
10
10-19

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents