CHAPTER 5: SETTINGS
The undervoltage delay setting defines the family of curves shown as follows.
where
T = operating time
D = undervoltage delay setting (D = 0.00 operates instantaneously)
V = secondary voltage applied to the relay
V
= pickup level
pickup
At 0% of pickup, the operating time equals the
5.7.9.2 Phase undervoltage (ANSI 27P, IEC PTUV)
SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  VOLTAGE ELEMENTS  PHASE UNDERVOLTAGE1(3)
 PHASE
 UNDERVOLTAGE1
L30 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
Figure 5-116: Inverse time undervoltage curves
PHASE UNDERVOLTAGE DELAY
PHASE UV1
FUNCTION: Disabled
PHASE UV1 SIGNAL
SOURCE: SRC 1
PHASE UV1 MODE:
Phase to Ground
PHASE UV1
PICKUP: 1.000 pu
PHASE UV1
CURVE: Definite Time
PHASE UV1
DELAY: 1.00 s
PHASE UV1 MINIMUM
VOLTAGE: 0.100 pu
PHASE UV1 BLOCK:
Off
GROUPED ELEMENTS
setting.
Range: Disabled, Enabled
Range: SRC 1, SRC 2
Range: Phase to Ground, Phase to Phase
Range: 0.004 to 3.000 pu in steps of 0.001
Range: Definite Time, Inverse Time
Range: 0.00 to 600.00 s in steps of 0.01
Range: 0.000 to 3.000 pu in steps of 0.001
Range: FlexLogic operand
Eq. 5-26
5
5-229