PILOT CHANNEL RELAYING
The slave L30 performs the following functions:
Samples currents and voltages
Removes DC offset from the current via the mimic algorithm
Creates phaselets
Calculates sum of squares data
Transmits current data to all master L30 relays
2
Performs all local relaying functions
Receives current differential DTT and Direct Input signals from all other L30 relays
Transmits direct output signals to all communicating relays
Sends synchronization information of local clock to all other L30 clocks
The master L30 relay performs the following functions:
Performs all functions of a slave L30
Receives current phasor information from all relays
Performs the current differential algorithm
Sends a current differential DTT signal to all L30 relays on the protected line
In the peer-to-peer mode, all L30 relays act as masters.