3-Phase 3-Wire ∆ Balanced (With 1 Current Sensor); 3-Phase 4-Wire Y Power Networks; 3-Phase 4-Wire Y (With 3 Current Sensors); Power & Energy Logger Model Pel 102 And Pel - AEMC PEL102 User Manual

Power energy logger
Hide thumbs Also See for PEL102:
Table of Contents

Advertisement

3.6.3.7 3-Phase 3-Wire ∆ balanced (with 1 current sensor)
For 3-Phase 3-Wire
current sensors:
Connect the terminal V1 test lead to the L1 phase
conductor
Connect the terminal V2 test lead to the L2 phase
conductor
Connect the terminal I3 current probe to the L3 phase
conductor
Ensure that the current arrow on the sensor is directed
towards the load. This ensures proper phase angle for power
measurements and other phase sensitive measurements.

3.6.4 3-Phase 4-Wire Y Power networks

3.6.4.1 3-Phase 4-Wire Y (with 3 current sensors)

For 3-Phase 4-Wire Y measurements using three current sensors:
Connect the terminal N test lead to the neutral conductor
Connect the terminal V1 test lead to the L1 phase conductor
Connect the terminal V2 test lead to the L2 phase conductor
Connect the terminal V3 test lead to the L3 phase conductor
Connect the terminal I1 current probe to the LI phase
conductor
Connect the terminal I2 current probe to the L2 phase
conductor
Connect the terminal I3 current probe to the L3 phase
conductor
Ensure that the current arrow on the sensor is directed towards the
load. This ensures proper phase angle for power measurements
and other phase sensitive measurements.
Power & Energy Logger Model PEL 102 and PEL 103
Find Quality Products Online at:
Balanced measurements using three
GlobalTestSupply
www.
L3
L2
L1
V1
V2
V3
N
I1
Figure 20
L3
N
L2
L1
V1
V2
V3
N
I1
Figure 21
.com
sales@GlobalTestSupply.com
L1
L2
L3
I2
I3
L1
L2
L3
N
I2
I3
25