3-Phase 4-Wire Y Balanced; 3-Phase 4-Wire Y 2½ Element - AEMC PEL102 User Manual

Power energy logger
Hide thumbs Also See for PEL102:
Table of Contents

Advertisement

3.6.4.2 3-Phase 4-Wire Y balanced

For 3-Phase 3-Wire Balanced Y measurements using three
current sensors:
Connect the terminal N test lead to the neutral conductor
Connect the terminal V1 test lead to the L1 phase
conductor
Connect the terminal I1 current probe to the L1 phase
conductor
Ensure that the current arrow on the sensor is directed towards
the load. This ensures proper phase angle for power measure-
ments and other phase.
3.6.4.3 3-Phase 4-Wire Y 2½ Element
For 3-Phase 4-Wire Y 2½ Element measurements and using
three current sensors:
Connect the terminal N test lead to the neutral conductor
Connect the terminal V1 test lead to the L1 phase
conductor
Connect the terminal V3 test lead to the L3 phase
conductor
Connect the terminal I1 current probe to the LI phase
conductor
Connect the terminal I2 current probe to the L2 phase
conductor
Connect the terminal I3 current probe to the L3 phase
conductor
Ensure that the current arrow on the sensor is directed towards
the load. This ensures proper phase angle for power measure-
ments and other phase sensitive measurements.
26
Find Quality Products Online at:
GlobalTestSupply
www.
L3
N
L2
L1
V1
V2
V3
N
I1
Figure 22
L3
N
L2
L1
V1
V2
V3
N
I1
Figure 23
Power & Energy Logger Model PEL 102 and PEL 103
.com
sales@GlobalTestSupply.com
L1
L2
L3
N
I2
I3
L1
L2
L3
N
I2
I3

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pel103Pel 102