Energy - Displayed Values - AEMC PEL102 User Manual

Power energy logger
Hide thumbs Also See for PEL102:
Table of Contents

Advertisement

(1)
3-Phase 3-Wire includes:
3-Phase 3-Wire ∆ (with 2 current sensors)
3-Phase 3-Wire ∆ (with 3 current sensors)
3-Phase 3-Wire Open ∆ (with 2 current sensors)
3-Phase 3-Wire Open ∆ (with 3 current sensors]
3-Phase 3-Wire Y (with 2 current sensors)
3-Phase 3-Wire Y (with 3 current sensors]
3-Phase 3-Wire ∆ Balanced (with 1 current sensor)
(2)
3-Phase 4-Wire includes:
3-Phase 4-Wire Y (with 3 current sensors)
3-Phase 4-Wire Y Balanced
3-Phase 4-Wire Y 2½ Element
3-Phase 4-Wire ∆
3-Phase 4-Wire Open-∆

3.7.2 Energy - Displayed Values

The PEL measures the typical energy readings used. In addition, it enables advanced measurements for specialists or
individuals doing in-depth analysis.
Individual power magnitudes for Power Flow Quadrants (per IEC 62053-23) are available by simply scrolling through each
screen display. The values in each quadrant are often used by engineers addressing power flow issues
The Energy measurements, which are time dependent (typically 10 or 15 minute integration or aggregation periods), are
displayed sequentially in screens showing all phases. Table 2 shows the readings per network type.
The down arrow ▼ scrolls downward and the up arrow ▲ scrolls upward through the displays.
Each display is reached by pressing the down arrow ▼.
Energies are measured from the beginning of the recording session. Partial energies are the energies measured for a
defined period (see §4.4.5).
Partial Energy is reached by pressing the
To reenter the Energy setting, simply push the down arrow ▼.
Definitions:
Ep+: Total Active Energy Imported (used by load) in kWh
Ep-: Total Active Energy Exported (to source) in kWh
Eq1: Active Energy Imported (by load) in Inductive Quadrant (Quadrant 1) in kvarh
Eq2: Active Energy Exported (to source) in Capacitive Quadrant (Quadrant 2) in kvarh
Eq3; Active Energy Exported (to source) in Inductive Quadrant (Quadrant 3) in kvarh
Eq4: Active Energy Imported (by load) in Capacitive Quadrant (Quadrant 4) in kvarh
Es+: Total Apparent Energy Imported (by load) in kVAh
Es-: Total Apparent Energy Exported (to source) in kVAh
Typically, industrial users will focus on the following values. The other values are used for load analysis and utilities.
kWh: Ep+ which is the traditional load Active Energy
kvarh: Eq1 which is the traditional load Reactive Energy
kVAh: Es+ which is the traditional load Apparent Energy
Power & Energy Logger Model PEL 102 and PEL 103
Find Quality Products Online at:
button for > 2 sec.
GlobalTestSupply
www.
.com
sales@GlobalTestSupply.com
31

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pel103Pel 102

Table of Contents