3.6.3.5 3-Phase 3-Wire Y (with 2 current sensors)

For 3-Phase 3-Wire Y measurements using two current
sensors:
Connect the terminal V1 test lead to the L1 phase
conductor
Connect the terminal V2 test lead to the L2 phase
conductor
Connect the terminal V3 test lead to the L3 phase
conductor
Connect the terminal I1 current probe to the LI phase
conductor
Connect the terminal I3 current probe to the L3 phase
conductor
Ensure that the current arrow on the sensor is directed
towards the load. This ensures proper phase angle for power
measurements and other phase sensitive measurements.
3.6.3.6 3-Phase 3-Wire Y (with 3 current sensors]
For 3-Phase 3-Wire Y measurements using three current
sensors:
Connect the terminal V1 test lead to the L1 phase
conductor
Connect the terminal V2 test lead to the L2 phase
conductor
Connect the terminal V3 test lead to the L3 phase
conductor
Connect the terminal I1 current probe to the LI phase
conductor
Connect the terminal I2 current probe to the L2 phase
conductor
Connect the terminal I3 current probe to the L3 phase
conductor
Ensure that the current arrow on the sensor is directed
towards the load. This ensures proper phase angle for power
measurements and other phase sensitive measurements.
24
Find Quality Products Online at:
GlobalTestSupply
www.
L3
N
L2
L1
V1
V2
V3
N
I1
Figure 18
L3
N
L2
L1
V1
V2
V3
N
I1
Figure 19