Remaining Connection Status; Parallel Redundancy Protocol (Prp) - GE L30 Instruction Manual

Line current differential system ur series
Hide thumbs Also See for L30:
Table of Contents

Advertisement

6.2 STATUS
PATH: ACTUAL VALUES
 COMM STATUS
 REMAINING CONNECT
These values specify the remaining number of TCP connections still available for each protocol. The display depends on
the options applicable to your device, for example the PMU entry does not display when not applicable. Each time a con-
nection is used, the remaining number of connections decrements. When released, the remaining number of connections
increments. If no connection is made over the specific protocol, the number equals the maximum number available for the
specific protocol.
For example, the maximum number of Modbus TCP connections is 4. Once an EnerVista session is opened on a computer
connected to the UR over Ethernet, the Modbus TCP status shows 3. If the EnerVista application is closed, the Modbus
TCP status shows 4.
— The number of IEC 61850 connections remaining.
MMS TCP
— The maximum number of PMU TCP connections matches the number of aggregators. The maximum number
PMU TCP
of aggregators for the N60 is 4. The maximum number for the C60 is 2. The maximum number is 1 for other products with
a PMU. The remaining number of aggregators displays here.
6
The Parallel Redundancy Protocol (PRP) defines a redundancy protocol for high availability in substation automation net-
works.
PATH: ACTUAL VALUES
 PRP
The L30 Line Current Differential System is provided with optional PRP capability. This feature is specified
as a software option at the time of ordering. See the Order Codes section in chapter 2 for details.
TOTAL RECEIVED PORT A
6-10

STATUS
COMM STATUS REMAINING CONNECT
MMS TCP(max 5)
5
MODBUS TCP(max 4)
MESSAGE
4
DNP TCP (max 2)
MESSAGE
2
IEC-104 (max 2)
MESSAGE
2
PMU TCP
MESSAGE
1

STATUS
PRP
Total Rx Port A:
Total Rx Port B:
MESSAGE
Total Errors:
MESSAGE
Mismatches Port A:
MESSAGE
Mismatches Port B:
MESSAGE
is a counter for total messages received (either from DANPs or from SANs) on Port A.
L30 Line Current Differential System

6.2.17 REMAINING CONNECTION STATUS

Range: 0 to 5
Range: 0 to 4
Range: 0 to 2
Range: 0 to 2
Range: 1 to 4

6.2.18 PARALLEL REDUNDANCY PROTOCOL (PRP)

Range: 0 to 4G, blank if PRP disabled
Range: 0 to 4G, blank if PRP disabled
Range: 0 to 4G, blank if PRP disabled
Range: 0 to 4G, blank if PRP disabled
Range: 0 to 4G, blank if PRP disabled
6 ACTUAL VALUES
GE Multilin