5 SETTINGS
b) DIRECT MESSAGES
Direct messages are used only between L30 relays connected directly using type 7 or type 2 digital communication cards.
These messages are transmitted every one-half of the power frequency cycle (10 ms for 50 Hz and 8.33 ms for 60 Hz) This
facility is of particular value for pilot schemes and transfer tripping. Direct messaging is available on both single channel
and dual channel communications modules. The inputs and outputs on communications channel 1 are numbered 1-1
through 1-8, and the inputs and outputs on communications channel 2 are numbered 2-1 through 2-8.
Settings associated with direct messages are automatically presented in accordance with the number of
channels provided in the communications module in a specific relay.
NOTE
c) LOCAL DEVICES: DEVICE ID FOR TRANSMITTING GSSE MESSAGES
In a L30 relay, the device ID that represents the IEC 61850 GOOSE application ID (GoID) name string sent as part of each
GOOSE message is programmed in the
GSSE/GOOSE CONFIGURATION
Likewise, the device ID that represents the IEC 61850 GSSE application ID name string sent as part of each GSSE mes-
sage is programmed in the
SETTINGS
CONFIGURATION
TRANSMISSION
In L30 releases previous to 5.0x, these name strings were represented by the
d) REMOTE DEVICES: ID OF DEVICE FOR RECEIVING GSSE/GOOSE MESSAGES

PATH: SETTINGS
INPUTS/OUTPUTS
 REMOTE DEVICE
1
MESSAGE
MESSAGE
Remote devices are available for setting purposes. A receiving relay must be programmed to capture messages from only
those originating remote devices of interest. This setting is used to select specific remote devices by entering (bottom row)
the exact identification (ID) assigned to those devices.
The
REMOTE DEVICE 1 ETYPE APPID
sages. This setting identifies the Ethernet application identification in the GOOSE message. It should match the corre-
sponding settings on the sending device.
The
REMOTE DEVICE 1 DATASET
DNA and UserSt bit pairs), or one of the configurable datasets.
Note that the dataset for the received data items must be made up of existing items in an existing logical node. For this rea-
son, logical node GGIO3 is instantiated to hold the incoming data items. GGIO3 is not necessary to make use of the
received data. The remote input data item mapping takes care of the mapping of the inputs to remote input FlexLogic oper-
ands. However, GGIO3 data can be read by IEC 61850 clients.
GE Multilin
SETTINGS
PRODUCT SETUP

TRANSMISSION
FIXED GOOSE

PRODUCT SETUP


setting.
GSSE
GSSE ID

REMOTE DEVICES
REMOTE DEVICE
Remote Device 1
REMOTE DEVICE
ETYPE APPID: 0
REMOTE DEVICE
DATASET: Fixed
setting is only used with GOOSE messages; they are not applicable to GSSE mes-
setting provides for the choice of the L30 fixed (DNA/UserSt) dataset (that is, containing
L30 Line Current Differential System

COMMUNICATIONS

setting.
GOOSE ID

COMMUNICATIONS
IEC 61850 PROTOCOL
RELAY NAME
REMOTE DEVICE 1(16)
Range: up to 20 alphanumeric characters
1 ID:
Range: 0 to 16383 in steps of 1
1
Range: Fixed, GOOSE 1 through GOOSE 16
1
5.8 INPUTS AND OUTPUTS

IEC 61850 PROTOCOL
GSSE/GOOSE
setting.
5-251
5