GE L30 Instruction Manual page 309

Line current differential system ur series
Hide thumbs Also See for L30:
Table of Contents

Advertisement

5 SETTINGS
IEC CURVES
For European applications, the relay offers three standard curves defined in IEC 255-4 and British standard BS142. These
are defined as IEC Curve A, IEC Curve B, and IEC Curve C. The formulae for these curves are:
T
=
where: T = operate time (in seconds), TDM = Multiplier setting, I = input current, I
constants, t
= characteristic constant, and T
r
and
is "Timed")
RESET
Table 5–24: IEC (BS) INVERSE TIME CURVE CONSTANTS
IEC (BS) CURVE SHAPE
IEC Curve A (BS142)
IEC Curve B (BS142)
IEC Curve C (BS142)
IEC Short Inverse
Table 5–25: IEC CURVE TRIP TIMES (IN SECONDS)
MULTIPLIER
(TDM)
1.5
2.0
IEC CURVE A
0.05
0.860
0.501
0.10
1.719
1.003
0.20
3.439
2.006
0.40
6.878
4.012
0.60
10.317
6.017
0.80
13.755
8.023
1.00
17.194
10.029
IEC CURVE B
0.05
1.350
0.675
0.10
2.700
1.350
0.20
5.400
2.700
0.40
10.800
5.400
0.60
16.200
8.100
0.80
21.600
10.800
1.00
27.000
13.500
IEC CURVE C
0.05
3.200
1.333
0.10
6.400
2.667
0.20
12.800
5.333
0.40
25.600
10.667
0.60
38.400
16.000
0.80
51.200
21.333
1.00
64.000
26.667
IEC SHORT TIME
0.05
0.153
0.089
0.10
0.306
0.178
0.20
0.612
0.356
0.40
1.223
0.711
0.60
1.835
1.067
0.80
2.446
1.423
1.00
3.058
1.778
GE Multilin
K
-------------------------------------- -
E
×
TDM
,
T
(
I I
)
1
RESET
pickup
RESET
K
E
0.140
0.020
13.500
1.000
80.000
2.000
0.050
0.040
CURRENT ( I / I
3.0
4.0
0.315
0.249
0.214
0.630
0.498
0.428
1.260
0.996
0.856
2.521
1.992
1.712
3.781
2.988
2.568
5.042
3.984
3.424
6.302
4.980
4.280
0.338
0.225
0.169
0.675
0.450
0.338
1.350
0.900
0.675
2.700
1.800
1.350
4.050
2.700
2.025
5.400
3.600
2.700
6.750
4.500
3.375
0.500
0.267
0.167
1.000
0.533
0.333
2.000
1.067
0.667
4.000
2.133
1.333
6.000
3.200
2.000
8.000
4.267
2.667
10.000
5.333
3.333
0.056
0.044
0.038
0.111
0.088
0.075
0.223
0.175
0.150
0.445
0.351
0.301
0.668
0.526
0.451
0.890
0.702
0.602
1.113
0.877
0.752
L30 Line Current Differential System
t
r
-------------------------------------- -
×
TDM
2
=
(
)
1
I I
pickup
pickup
= reset time in seconds (assuming energy capacity is 100%
T
R
9.7
43.2
58.2
0.500
)
pickup
5.0
6.0
7.0
0.192
0.176
0.384
0.353
0.767
0.706
1.535
1.411
2.302
2.117
3.070
2.822
3.837
3.528
0.135
0.113
0.270
0.225
0.540
0.450
1.080
0.900
1.620
1.350
2.160
1.800
2.700
2.250
0.114
0.083
0.229
0.167
0.457
0.333
0.914
0.667
1.371
1.000
1.829
1.333
2.286
1.667
0.034
0.031
0.067
0.062
0.135
0.124
0.269
0.247
0.404
0.371
0.538
0.494
0.673
0.618
5.6 GROUPED ELEMENTS
(EQ 5.11)
= Pickup Current setting, K, E =
8.0
9.0
10.0
0.165
0.156
0.149
0.330
0.312
0.297
0.659
0.623
0.594
1.319
1.247
1.188
1.978
1.870
1.782
2.637
2.493
2.376
3.297
3.116
2.971
0.096
0.084
0.075
0.193
0.169
0.150
0.386
0.338
0.300
0.771
0.675
0.600
1.157
1.013
0.900
1.543
1.350
1.200
1.929
1.688
1.500
0.063
0.050
0.040
0.127
0.100
0.081
0.254
0.200
0.162
0.508
0.400
0.323
0.762
0.600
0.485
1.016
0.800
0.646
1.270
1.000
0.808
0.029
0.027
0.026
0.058
0.054
0.052
0.115
0.109
0.104
0.231
0.218
0.207
0.346
0.327
0.311
0.461
0.435
0.415
0.576
0.544
0.518
5-169
5