GE L30 Instruction Manual page 234

Line current differential system ur series
Hide thumbs Also See for L30:
Table of Contents

Advertisement

5.4 SYSTEM SETUP
The disturbance detector responds to the change in currents of twice the current cut-off level. The default cut-off threshold
is 0.02 pu; thus by default the disturbance detector responds to a change of 0.04 pu. The metering sensitivity setting (

UCT SETUP
DISPLAY PROPERTIES
accordingly.
EXAMPLE USE OF SOURCES:
An example of the use of sources is shown in the diagram below. A relay could have the following hardware configuration:
INCREASING SLOT POSITION LETTER -->
CT/VT MODULE 1
CTs
This configuration could be used on a two-winding transformer, with one winding connected into a breaker-and-a-half sys-
tem. The following figure shows the arrangement of sources used to provide the functions required in this application, and
the CT/VT inputs that are used to provide the data.
5
Y LV
SRC 1
Phase CT
M1
Ground CT
M1
Phase VT
M5
Aux VT
None
5-94

CURRENT CUT-OFF LEVEL
CT/VT MODULE 2
CT/VT MODULE 3
VTs
not applicable
Figure 5–19: EXAMPLE USE OF SOURCES
D HV
AUX
SRC 2
SRC 3
F1+F5
None
None
None
None
None
None
U1
L30 Line Current Differential System
) controls the sensitivity of the disturbance detector
5 SETTINGS