GE L30 Instruction Manual page 197

Line current differential system ur series
Hide thumbs Also See for L30:
Table of Contents

Advertisement

5 SETTINGS
o) IEC 60870-5-104 PROTOCOL
PATH: SETTINGS
PRODUCT SETUP
 IEC 60870-5-104
 PROTOCOL
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The L30 supports the IEC 60870-5-104 protocol. This protocol is enabled when the
setting is set to IEC 60870-5-104. The L30 can be used as an IEC 60870-5-104 slave device
MUNICATIONS
PROTOCOL
connected to a maximum of two masters (usually either an RTU or a SCADA master station). Since the L30 maintains two
sets of IEC 60870-5-104 data change buffers, no more than two masters should actively communicate with the L30 at one
time.
The
IEC ------- DEFAULT THRESHOLD
M_ME_NC_1 analog data. These settings group the L30 analog data into types: current, voltage, power, energy, and other.
Each setting represents the default threshold value for all M_ME_NC_1 analog points of that type. For example, to trigger
spontaneous responses from the L30 when any current values change by 15 A, the
ting should be set to 15. Note that these settings are the default values of the deadbands. P_ME_NC_1 (parameter of mea-
sured value, short floating point value) points can be used to change threshold values, from the default, for each individual
M_ME_NC_1 analog point. Whenever power is removed and re-applied to the L30, the default thresholds are in effect.
The
setting decides whether multiple client connections are accepted or not. If redundancy is set to Yes,
IEC REDUNDANCY
two simultaneous connections can be active at any given time.
: When set to 0, the change takes effect when the L30 is restarted.
IEC TCP PORT NUMBER
IEC COMMON ADDRESS OF ASDU
: The change takes effect when the L30 is restarted.
IEC CYCLIC DATA PERIOD
Do not set more than one protocol to the same TCP/UDP port number, as this results in unreliable operation of
those protocols.
NOTE
The L30 relay does not support energy metering. As such, the
cable.
NOTE
GE Multilin


COMMUNICATIONS
IEC TCP PORT
NUMBER: 2404
 IEC NETWORK
 CLIENT ADDRESSES
IEC COMMON ADDRESS
OF ASDU:
0
IEC CYCLIC DATA
PERIOD:
60 s
IEC CURRENT DEFAULT
THRESHOLD: 30000
IEC VOLTAGE DEFAULT
THRESHOLD: 30000
IEC POWER DEFAULT
THRESHOLD: 30000
IEC ENERGY DEFAULT
THRESHOLD: 30000
IEC PF DEFAULT
THRESHOLD: 1.00
IEC OTHER DEFAULT
THRESHOLD: 30000
IEC REDUNDANCY
ENABLED: No
settings are used to determine when to trigger spontaneous responses containing
: The change takes effect when the L30 is restarted.
L30 Line Current Differential System
IEC 60870-5-104 PROTOCOL
Range: 0 to 65535 in steps of 1
Range: see sub-menu below
Range: 0 to 65535 in steps of 1
Range: 1 to 65535 s in steps of 1
Range: 0 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1
Range: 0.00 to 1.00
Range: 0 to 65535 in steps of 1
Range: No, Yes
SETTINGS
IEC CURRENT DEFAULT THRESHOLD
IEC ENERGY DEFAULT THRESHOLD
5.2 PRODUCT SETUP

PRODUCT SETUP
COM-
set-
setting is not appli-
5-57
5