GE L30 Instruction Manual page 302

Line current differential system ur series
Hide thumbs Also See for L30:
Table of Contents

Advertisement

5.6 GROUPED ELEMENTS
nal CTs (where CT
performed against the remote CT with the maximum CT primary defined by the
through
CURRENT DIFF SIGNAL SOURCE 4
settings chapter for additional details.
When in-zone power transformer is present, this setting should be calculated and used by taking into account the in-
zone power transformer as follows.
CT Tap
In this equation, V
primary nominal voltage of the transformer winding at the local terminal.
CURRENT DIFF RESTRAINT 1 and CURRENT DIFF RESTRAINT 2: These settings select the bias characteristic for
the first and second slope, respectively.
CURRENT DIFF BREAK PT: This setting is used to select an intersection point between the two slopes.
INRUSH INHIBIT MODE: This setting selects the mode for blocking differential protection during magnetizing inrush
conditions. Modern transformers can produce small second harmonic ratios during inrush conditions. This can result
undesired tripping of the protected line. Reducing the second harmonic inhibit threshold may jeopardize dependability
and speed of differential protection. When low, the second harmonic ratio causes problems in one phase only. This
may be utilized as a mean to ensure security by applying cross-phase blocking rather than lowering the inrush inhibit
threshold.
If set to "Disabled", no inrush inhibit action is taken.
If set to "Per phase", the L30 performs inrush inhibit individually in each phase.
5
If set to "2-out-of-3", the L30 checks second harmonic level in all three phases individually. If any two phases
establish an inhibiting condition, then the remaining phase is restrained automatically.
If set to "Average", the L30 first calculates the average second harmonic ratio, then applies the inrush threshold to
the calculated average.
INRUSH INHIBIT LEVEL: This setting specifies the level of second harmonic component in the transformer magnetiz-
ing inrush current, above which the current differential element is inhibited from operating. The value of the
setting must be taken into account when programming this value. This setting is typically programmed as
INHIBIT MODE
"20% f
".
0
CURRENT DIFF GND FUNCTION: This setting enables and disabled the 87LG neutral differential element, which may
be used to detect high-resistive faults. This element uses restrained characteristics to cope with spurious zero-
sequence current during system unbalance and signal distortions. The differential neutral current is calculated as the
vector sum of all in-zone CT input neutral currents. The restraint current is derived as the maximum of phase currents
from all terminals flowing through any individual CT, including breaker-and-a-half configurations. The 87LG neutral dif-
ferential element is blocked when the phase current at any terminal is greater than 3 pu, since the phase differential
element should operate for internal faults. To correctly derive the restraint quantity from the maximum through current
at any terminal, it is important that the 87L phase-segregated differential pickup and slope settings are equal at all ter-
minals. Refer to the Applications of settings chapter for additional details.
CURRENT DIFF GND PICKUP: This setting specifies the pickup threshold for neutral current differential element.
CURRENT DIFF GND RESTRAINT: This setting specifies the bias characteristic for the neutral current differential ele-
ment.
CURRENT DIFF GND DELAY: This setting specifies the operation delay for the neutral current differential element.
Since this element is used to detect high-resistive faults where fault currents are relatively low, high-speed operation is
usually not critical. This delay will provide security against spurious neutral current during switch-off transients and
external fault clearing.
CURRENT DIFF DTT: This setting enables and disables the sending of a DTT by the current differential element on
per single-phase basis to remote devices. To allow the L30 to restart from master-master to master-slave mode (very
important on three-terminal applications),
CURRENT DIFF KEY DTT: This setting selects an additional protection element (besides the current differential ele-
ment; for example, distance element or breaker failure) which keys the DTT on a per three-phase basis.
5-162
/ CT
is referred to as the CT primary rated current). Ratio matching must always be
prim_rem
prim_loc
settings. See the Current differential settings example in the Application of
×
CT
V
prim_rem
prim_rem
-------------------------------------------------------- for remote terminals 1 and 2, respecitvely
=
×
CT
V
prim_loc
prim_loc
is primary nominal voltage of the transformer winding at the remote terminal and V
prim_rem
CURR DIFF DTT
L30 Line Current Differential System
CURRENT DIFF SIGNAL SOURCE 1
must be set to "Enabled".
5 SETTINGS
(EQ 5.9)
is
prim_loc
INRUSH
GE Multilin