Channel Monitor - GE L30 Instruction Manual

Line current differential system ur series
Hide thumbs Also See for L30:
Table of Contents

Advertisement

2.4 PILOT CHANNEL RELAYING
Performs all functions of a slave L30
Receives current phasor information from all relays
Performs the current differential algorithm
Sends a current differential DTT signal to all L30 relays on the protected line
In the peer-to-peer mode, all L30 relays act as masters.
2
The L30 has logic to detect that the communications channel is deteriorating or has failed completely. This can provide an
alarm indication and disable the current differential protection. Note that a failure of the communications from the master to
a slave does not prevent the master from performing the current differential algorithm; failure of the communications from a
slave to the master will prevent the master from performing the correct current differential logic. Channel propagation delay
is being continuously measured and adjusted according to changes in the communications path. Every relay on the protec-
tion system can assigned an unique ID to prevent advertent loopbacks at multiplexed channels.
2-22
Tx
Rx
IED-1
Tx
Optional redundant channel
Rx
Typical two-terminal application
Tx
Rx
IED-1
Tx
Rx
Typical three-terminal application
Figure 2–4: COMMUNICATIONS PATHS
L30 Line Current Differential System
2 PRODUCT DESCRIPTION
Rx
Tx
Rx
Tx
Rx
Tx
Rx
Tx
Tx
Rx
Tx
Rx
CHn
CHn
IED-3

2.4.2 CHANNEL MONITOR

IED-2
IED-2
831009A5.CDR