B.4 MEMORY MAPPING
Table B–10: MODBUS MEMORY MAP (Sheet 22 of 63)
ADDR
REGISTER NAME
406F
Number of Channels
4070
Number of Terminals
4071
Positive Sequence Reactance
4072
Round Trip Time
4073
Terminal 1 ID
B
4074
Terminal 2 ID
4075
Zero-Sequence Current Removal
4076
Zero Sequence Reactance
Communications (Read/Write Setting)
407D
COM2 Selection
407E
COM1 Minimum Response Time
407F
COM2 Minimum Response Time
4080
Modbus Slave Address
4083
RS485 Com1 Baud Rate
4084
RS485 Com1 Parity
4085
RS485 Com2 Baud Rate
4086
RS485 Com2 Parity
4087
Port 1 IP Address
4089
Port 1 IP Subnet Mask
408B
Port 1 Gateway IP Address
408D
Network Address NSAP
4097
Port 1 Link Loss Alert
4098
Port 2 Link Loss Alert
4099
Port 3 Link Loss Alert
409A
DNP Channel 1 Port
409B
DNP Channel 2 Port
409C
DNP Address
409E
DNP Client Addresses (2 items)
40A3
TCP Port Number for the Modbus protocol
40A4
TCP/UDP Port Number for the DNP Protocol
40A5
TCP Port Number for the HTTP (Web Server) Protocol
40A6
Main UDP Port Number for the TFTP Protocol
40A7
Data Transfer UDP Port Numbers for the TFTP Protocol
(zero means "automatic") (2 items)
40A9
DNP Unsolicited Responses Function
40AA
DNP Unsolicited Responses Timeout
40AB
DNP Unsolicited Responses Maximum Retries
40AC
DNP Unsolicited Responses Destination Address
40AD
Ethernet Operation Mode
40AE
DNP Current Scale Factor
40AF
DNP Voltage Scale Factor
40B0
DNP Power Scale Factor
40B1
DNP Energy Scale Factor
40B2
DNP Power Scale Factor
40B3
DNP Other Scale Factor
40B4
DNP Current Default Deadband
40B6
DNP Voltage Default Deadband
40B8
DNP Power Default Deadband
40BA
DNP Energy Default Deadband
40BC
DNP Power Factor Default Deadband
40BE
DNP Other Default Deadband
40C0
DNP IIN Time Synchronization Bit Period
40C1
DNP Message Fragment Size
40C2
DNP Client Address 3
B-30
RANGE
1 to 2
2 to 3
0.1 to 65.535
0 to 10
0 to 255
0 to 255
0 to 1
0.1 to 65.535
0 to 3
0 to 1000
0 to 1000
1 to 254
0 to 11
0 to 2
0 to 11
0 to 2
0 to 4294967295
0 to 4294967295
0 to 4294967295
---
0 to 1
0 to 1
0 to 1
0 to 5
0 to 5
0 to 65519
0 to 4294967295
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 1
0 to 60
1 to 255
0 to 65519
0 to 1
0 to 8
0 to 8
0 to 8
0 to 8
0 to 8
0 to 8
0 to 100000000
0 to 100000000
0 to 100000000
0 to 100000000
0 to 100000000
0 to 100000000
1 to 10080
30 to 2048
0 to 4294967295
L30 Line Current Differential System
APPENDIX B
UNITS
STEP
FORMAT
---
1
F001
---
1
F001
kohms
0.001
F001
ms
0.1
F001
---
1
F001
---
1
F001
---
1
F102
kohms
0.001
F001
---
1
F601
ms
10
F001
ms
10
F001
---
1
F001
---
1
F112
---
1
F113
---
1
F112
---
1
F113
---
1
F003
---
1
F003
---
1
F003
---
---
F074
---
1
F102
---
1
F102
---
1
F102
---
1
F177
---
1
F177
---
1
F001
---
1
F003
---
1
F001
---
1
F001
---
1
F001
---
1
F001
---
1
F001
---
1
F102
s
1
F001
---
1
F001
---
1
F001
---
1
F192
1 (Full-Duplex)
---
1
F194
---
1
F194
---
1
F194
---
1
F194
---
1
F194
---
1
F194
---
1
F003
---
1
F003
---
1
F003
---
1
F003
--
1
F003
---
1
F003
min
1
F001
---
1
F001
---
1
F003
DEFAULT
1
2
100
15
0
0
0 (Disabled)
100
0 (RS485)
0
0
254
8 (115200)
0 (None)
8 (115200)
2 (Even)
2130706433
4278190080
56554497
0
0 (Disabled)
0 (Disabled)
0 (Disabled)
0 (None)
0 (None)
1
0
502
20000
80
69
0
0 (Disabled)
5
10
1
2 (1)
2 (1)
2 (1)
2 (1)
2 (1)
2 (1)
30000
30000
30000
30000
30000
30000
1440
240
0
GE Multilin