GE L30 Instruction Manual page 181

Line current differential system ur series
Hide thumbs Also See for L30:
Table of Contents

Advertisement

5 SETTINGS
PATH: SETTINGS
PRODUCT SETUP
 ANALOG INPUT / MME
 POINTS
MESSAGE
MESSAGE
Up to 256 analog input points can be configured for the DNP or IEC 60870-5-104 protocols. The analog point list is config-
ured by assigning an appropriate FlexAnalog parameter to each point. Refer to Appendix A: FlexAnalog Parameters for the
full range of assignable parameters.
The DNP / IEC 60870-5-104 point lists always begin with point 0 and end at the first "Off" value. Since DNP / IEC
60870-5-104 point lists must be in one continuous block, any points assigned after the first "Off" point are ignored.
NOTE
Changes to the DNP / IEC 60870-5-104 point lists will not take effect until the L30 is restarted.
NOTE
l) IEC 61850 PROTOCOL
PATH: SETTINGS
PRODUCT SETUP
 IEC 61850 PROTOCOL
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The L30 Line Current Differential System is provided with optional IEC 61850 communications capability.
This feature is specified as a software option at the time of ordering. See the Order Codes section in chap-
ter 2 for details.
GE Multilin


COMMUNICATIONS
DNP / IEC104 POINT LISTS
Point:
0
Off
Point:
1
Off
Point:
255
Off


COMMUNICATIONS
IEC 61850 PROTOCOL
 GSSE / GOOSE
 CONFIGURATION
 SERVER
 CONFIGURATION
 IEC 61850 LOGICAL
 NODE NAME PREFIXES
 MMXU DEADBANDS
 GGIO1 STATUS
 CONFIGURATION
 GGIO2 CONTROL
 CONFIGURATION
 GGIO4 ANALOG
 CONFIGURATION
 GGIO5 UINTEGER
 CONFIGURATION
 REPORT CONTROL
 CONFIGURATION
 XCBR
 CONFIGURATION
 XSWI
 CONFIGURATION
L30 Line Current Differential System
5.2 PRODUCT SETUP

ANALOG INPUT / MME POINTS
Range: any FlexAnalog parameter
Range: any FlexAnalog parameter
Range: any FlexAnalog parameter
5
5-41

Advertisement

Table of Contents
loading

Table of Contents