Iec 61850 Goose Integers - GE L30 Instruction Manual

Line current differential system ur series
Hide thumbs Also See for L30:
Table of Contents

Advertisement

5 SETTINGS
When using GOOSE Analogs and PU base in FlexElements, the largest value that can be displayed in the FlexEle-
ment actual values is 2,140,000.000.
Table 5–34: GOOSE ANALOG INPUT BASE UNITS
ELEMENT
87L SIGNALS
(Local IA Mag, IB, and IC)
(Diff Curr IA Mag, IB, and IC)
(Terminal 1 IA Mag, IB, and IC)
(Terminal 2 IA Mag, IB and IC)
87L SIGNALS
(Op Square Curr IA, IB, and IC)
(Rest Square Curr IA, IB, and IC)
BREAKER ARCING AMPS
(Brk X Arc Amp A, B, and C)
dcmA
FREQUENCY
PHASE ANGLE
POWER FACTOR
RTDs
SOURCE CURRENT
SOURCE POWER
SOURCE VOLTAGE
SYNCHROCHECK
(Max Delta Volts)
The GOOSE analog input FlexAnalog values are available for use in other L30 functions that use FlexAnalog values.

PATH: SETTINGS
INPUTS/OUTPUTS
 GOOSE UINTEGER
 INPUT 1
MESSAGE
The IEC 61850 GOOSE uinteger inputs feature allows the transmission of FlexInteger values between any two UR-series
devices. The following settings are available for each GOOSE uinteger input.
UINTEGER 1 DEFAULT: This setting specifies the value of the GOOSE uinteger input when the sending device is
offline and the
UINTEGER 1 DEFAULT MODE
number.
UINTEGER 1 DEFAULT MODE: When the sending device is offline and this setting is "Last Known", the value of the
GOOSE uinteger input remains at the last received value. When the sending device is offline and this setting value is
"Default Value", then the value of the GOOSE uinteger input is defined by the
The GOOSE integer input FlexInteger values are available for use in other L30 functions that use FlexInteger values.
GE Multilin
BASE UNITS
I
= maximum primary RMS value of the +IN and –IN inputs
BASE
(CT primary for source currents, and 87L source primary current for line differential currents)
BASE = Squared CT secondary of the 87L source
2
BASE = 2000 kA
× cycle
BASE = maximum value of the
DCMA INPUT MAX
under the +IN and –IN inputs.
f
= 1 Hz
BASE
ϕ
= 360 degrees (see the UR angle referencing convention)
BASE
PF
= 1.00
BASE
BASE = 100°C
I
= maximum nominal primary RMS value of the +IN and –IN inputs
BASE
P
= maximum value of V
BASE
BASE
V
= maximum nominal primary RMS value of the +IN and –IN inputs
BASE
V
= maximum primary RMS value of all the sources related to the +IN and –IN inputs
BASE

IEC 61850 GOOSE UINTEGERS
UINTEGER
1 DEFAULT:
1000
UINTEGER
1 DEFAULT
MODE: Default Value
is set to "Default Value".This setting is stored as a 32-bit unsigned integer
L30 Line Current Differential System
5.8 INPUTS AND OUTPUTS
setting for the two transducers configured
× I
for the +IN and –IN inputs
BASE

5.8.12 IEC 61850 GOOSE INTEGERS


GOOSE UINTEGER INPUT 1(16)
Range: 0 to 429496295 in steps of 1
Range: Default Value, Last Known
UINTEGER 1 DEFAULT
5
setting.
5-257