5.7 CONTROL ELEMENTS
The 61850 standard provides for the ability to monitor, edit, and change setting groups in a relay through a series of ser-
vices operating on Setting Group Control Block values. There is one SGCB in LLN0 in LD1 in the UR as, at present, the
other LDs do not support multiple setting groups The default value of
or UR setting group control to function, the
The active setting group in the UR is settable from either the value set via a FlexLogic operand in the UR (present practice)
or a SelectActiveSG command from a 61850 Client. For both the UR and IEC 61850, the default active setting group is "1".
A 61850 SelectActiveSG command sets one of the internal Non-Volatile flags (61850 SG Level x) that represents the
requested Active Setting Group shown as follows:
Table 5–31: ACTIVE SETTING GROUP
SELECTACTIVESG VALUE
1 (default)
2
3
4
5
6
On power-up or restart, the previously selected 61850 SG Level x is re-instated. Similarly, the input to the setting group
control in the UR can be designed with Non-Volatile latches to achieve the same effect.
The setting groups menu controls the activation and deactivation of up to six possible groups of settings in the
settings menu. The faceplate Settings In Use LEDs indicate which active group (with a non-flashing energized
ELEMENTS
LED) is in service.
5
The
SETTING GROUPS BLK
"On". This can be useful in applications where it is undesirable to change the settings under certain conditions, such as the
breaker being open.
The
GROUP 2 ACTIVATE ON
ular setting group active for use by any grouped element. A priority scheme ensures that only one group is active at a given
time – the highest-numbered group that is activated by its
groups. There is no activate on setting for group 1 (the default active group), because group 1 automatically becomes
active if no other group is active.
The
SETTING GROUP 1 NAME
groups. Once programmed, this name appears on the second line of the
display.
The relay can be set up via a FlexLogic equation to receive requests to activate or de-activate a particular non-default set-
tings group. The following FlexLogic equation (see the following figure) illustrates requests via remote communications (for
example,
VIRTUAL INPUT 1 ON
lar settings group, and requests from several overcurrent pickup measuring elements to inhibit the use of the particular set-
tings group. The assigned
5-210
SETTING GROUPS FUNCTION
FLAG SET
SG Level 1
SG Level 2
SG Level 3
SG Level 4
SG Level 4
SG Level 6
setting prevents the active setting group from changing when the FlexLogic parameter is set to
to
settings select a FlexLogic operand which, when set, makes the partic-
GROUP 6 ACTIVATE ON
to
settings allows the user to assign a name to each of the six settings
SETTING GROUP 6 NAME
) or from a local contact input (for example,
operand is used to control the "On" state of a particular settings group.
VIRTUAL OUTPUT 1
L30 Line Current Differential System
is Disabled. In order for 61850 and/
SETTING GROUPS
must be set to Enabled.
parameter takes priority over the lower-numbered
ACTIVATE ON
GROUPED ELEMENTS
CONTACT IP 1 ON
5 SETTINGS
GROUPED
menu
SETTING GROUP 1(6)
) to initiate the use of a particu-
GE Multilin